3. Operations

Testing the FTP upload configuration:

This test validates that the unit is able to contact and log onto the specified FTP server, download the firmware
file and verify that the firmware file is valid for this unit.

Press

Test

.

SNTP

The SNTP configuration page is used for setup and maintenance of SNTP support.

Setting the SNTP Server Address:

Enter the IP address in the primary and/or secondary address field and press

Apply

.

SNMP

The SNMP configuration page is used for setup and maintenance of all settings required to enable SNMP
support as well as access to the trap configuration pages. For additional information on SNMP support and
detailed descriptions of available traps, see on page 34.

NOTE: Traps are generated according to a hierarchical architecture; i.e. if a Tower Status enters a trap
condition, only the Tower Status trap is generated. Infeed and Outlet Status traps are suppressed until the
Tower Status returns to Normal.

Enabling or disabling SNMP support:

Select

Enabled

or

Disabled

from the drop-down menu and press

Apply

.

Setting the community strings:

Enter the community string in the appropriate field and press

Apply

.

Community strings may be 1 to 24 characters

Setting the trap timer:

Enter a trap timer value in the Error Trap Repeat Time field and press

Apply

.

The Error Trap Repeat Time value may be 1 to 65535 (in seconds).

Setting trap destinations:

Enter an IP address in the appropriate Trap Destination field and press

Apply

.

Enabling or disabling tower traps:

Click on the

Tower Traps

link.

On the subsequent Tower Traps page, select or deselect the desired traps and press

Apply

.

Configuring input feed traps:

Click on the

Input Feed Traps

link.

On the subsequent Input Feed Traps page, select or deselect the desired traps and press

Apply

.

For Load traps, enter a maximum load value for the infeed in the High Load Threshold field and press

Apply

.

The High Load Threshold value may be 0 to 255 (in amperes).

Page 16 - 301-0399-3 Rev A.