Advanced operations – American Power Conversion AmpMeter PDU User Manual

Page 42

Advertising
background image

4. Advanced Operations

Enabling or Disabling a Load trap

The Set Trap Infeed Load command is used to enable or disable an Infeed Load trap.

To Enable or Disable a Load trap:

At the AmpMeter PDU: prompt, type

set trap infeed load

, followed by the infeed name, and

on

or

off

.

Press

Enter

, or

Type

set trap infeed

load all

, followed by

on

or

off

and press

Enter

.

Examples

The following command enables the Load trap for second infeed on the first tower, using the infeed’s absolute
name:

AmpMeter PDU: set trap infeed load .AB on<Enter>

The following command disables the Load trap for all infeeds:

AmpMeter PDU: set trap infeed load all off<Enter>

NOTE: Enabling lower hierarchical traps automatically enables traps of higher hierarchical value: i.e. enabling
an Infeed Load trap automatically enables the Infeed and Tower Status traps for that infeed.

Setting the Infeed Load limit

The Set Trap Infeed Loadhigh command is used to set the upper load limits for an input feed.

To set the infeed load limit:

At the AmpMeter PDU: prompt, type

set trap infeed loadhigh

, followed by the infeed name, and a value

from 0 to 255 in amperes. Press

Enter

.

Example

The following command sets the infeed load limit for the second infeed on the first tower to 25 amperes, using
the infeed’s absolute name:

AmpMeter PDU: set trap infeed loadhigh .ab 25<Enter>

Enabling or Disabling a Change trap

The Set Trap Outlet Change command is used to enable or disable an Outlet Change trap.

To Enable or Disable a Change trap:

At the AmpMeter PDU: prompt, type

set trap outlet change

, followed by the outlet name and

on

or

off

.

Press

Enter

, or

Type

set trap outlet

change all

, followed by

on

or

off

and press

Enter

.

Example

The following command enables the Change trap for the third outlet on the first infeed of the second tower,
using the outlet’s absolute name:

AmpMeter PDU: set trap outlet change .ba3 on<Enter>

Enabling or Disabling the Temp trap

The Set Trap THS Temp command is used to enable or disable the Temp trap.

To Enable or Disable the Temp trap:

At the AmpMeter PDU: prompt, type

set trap ths temp

, followed by the sensor name and

on

or

off

. Press

Enter

.

Example

The following command enables the Temp trap for the first temperature-humidity sensor:

AmpMeter PDU: set trap ths temp .a1 on<Enter>

Page 42 - 301-0399-3 Rev A.