Configuring traps, Configuring traps 41, Advanced operations – American Power Conversion AmpMeter PDU User Manual

Page 41

Advertising
background image

4. Advanced Operations

Configuring Traps

SNMP Trap Command Summary

Command Description

Set Trap EM Status

Enables or disables the Environmental Monitor Status trap

Set Trap THS Status

Enables or disables a temperature/humidity sensor Status trap

Set Trap THS Temp

Enables or disables a temperature/humidity sensor Temp trap

Set Trap THS Temphigh

Sets a temperature/humidity sensor Temp trap high limit

Set Trap THS Templow

Sets a temperature/humidity sensor Temp trap low limit

Set Trap THS Humid

Enables or disables a temperature/humidity sensor Humid trap

Set Trap THS Humidhigh

Sets a temperature/humidity sensor Humid trap high limit

Set Trap Tower Status

Enables or disables the Tower Status trap

Set Trap Infeed Status

Enables or disables the Infeed Status trap off

Set Trap Infeed Load

Enables or disables the Infeed Load trap

Set Trap Infeed HighThresh

Sets the Infeed Load trap high limit

Set Trap Outlet Change

Enables or disables the Outlet Change trap

Set Trap Outlet Status

Enables or disables the Outlet Status trap

Show Traps

Displays trap configurations

Enabling or Disabling a Status trap

The Set Trap … Status command is used to enable or disable Status traps for a Tower, Infeed, Outlet,
Environmental Monitor or Sensor.

To Enable or Disable a Status trap:

At the AmpMeter PDU: prompt, type

set trap

(

tower

,

infeed,

outlet, em

or

ths

)

status

, followed by the

tower, infeed, outlet, Environmental Monitor or sensor name, and

on

or

off

.

Press

Enter

, or

Type

set trap

(

tower

,

infeed,

outlet, em

or

ths

)

status all

, followed by

on

or

off

and press

Enter

.

Examples

The following command enables the Status trap for the first tower, using the tower’s absolute name:

AmpMeter PDU: set trap tower status .a on<Enter>

The following command enables the Status trap for the tower named Florida_HQ_1:

AmpMeter PDU: set trap tower status Florida_HQ_1 on<Enter>

NOTE: Enabling lower hierarchical traps automatically enables traps of higher hierarchical value: i.e. enabling
an Outlet Status trap automatically enables the Infeed and Tower Status traps for that outlet. Conversely, if a
Tower Status trap is disabled, all associated Infeed Status & Load and Outlet Status traps will be disabled.

301-0399-3 Rev A. - Page 41