4. Advanced Operations

SNMP

The AmpMeter PDU family of products supports the Simple Network Management Protocol (SNMP). This
allows network management systems to use SNMP requests to retrieve information and control power for the
individual outlets.

The AmpMeter PDU includes an SNMP v1 agent supporting standard MIB I and MIB II objects.

NOTE: For security, SNMP support is disabled by default.

SNMP Command Summary

Command Description

Set snmp

Enables or disables SNMP support

Set snmp getcomm

Sets the ‘get’ community string

Set snmp setcomm

Sets the ‘set’ community string

Set snmp trapdest1

Sets a destination IP addresses for traps

Set snmp trapdest2

Sets a destination IP addresses for traps

Set snmp traptime

Sets the delay for steady state condition traps

Show snmp

Displays all SNMP configuration information

Enabling and Setting up SNMP Support

AmpMeter PDU SNMP support must be enabled and configured for access to AmpMeter PDU3 MIB objects
and generation of all AmpMeter PDU3 traps.

Enabling/disabling SNMP support

The AmpMeter PDU SNMP command is used to enable or disable SNMP support.

To enable SNMP support:

At the AmpMeter PDU: prompt, type

set snmp

, followed by

enabled

or

disabled

and press

Enter

.

NOTE: A restart of the AmpMeter PDU is required after enabling or disabling SNMP support. See Performing
a warm boot
on page 28 fo
r more information.

Setting trap destinations

The Set SNMP Trapdest1 and Trapdest2 commands are used to set the IP addresses of SNMP management
stations receiving all traps. AmpMeter PDU supports a maximum of two trap destinations; one must be defined
to enable trap generation.

To set the trap destination:

At the AmpMeter PDU: prompt, type

set snmp, trapdest1

or

trapdest2

, the Ipaddress and press

Enter

.

Example

The following sets the trap destination 1 to 64.42.31.208:

AmpMeter PDU: set snmp trapdest1 64.42.31.208<Enter>

To reset the trap destination:

At the AmpMeter PDU: prompt, type

set snmp, trapdest1

or

trapdest2, 0.0.0.0

and press

Enter

.

Page 36 - 301-0399-3 Rev A.