Data connections, Branch circuit protection, Appendices – American Power Conversion AmpMeter PDU User Manual

Page 49

Advertising
background image

5. Appendices

301-0399-3 Rev A. - Page 49

Data Connections

RS-232 port

The AmpMeter PDU may be equipped standard with an RJ45 DTE RS-232c serial port. This connector may be
used for direct local access or from other serial devices such as a terminal server. An RJ45 crossover cable is
provided for connection to an RJ45 DCE serial port.

Pin

DTE Signal Name

Input/Output

1

Request to Send

RTS

Output

2

Data Terminal Ready DTR

Output

6

7 54321

8

3

Transmit Data

TD

Output

4 Signal

Ground

5

Signal Ground

6

Receive Data

RD

Input

7

Data Set Ready

DSR

Input

8

Clear to Send

CTS

Input

RJ45 to DB9F serial port adapter

An RJ45 to DB9F serial port adapter may be provided for use in conjunction with the RJ45 crossover cable to
connect to a PC DB9M DCE serial port. The adapter pinouts below reflect use of the adapter with the provided
RJ45 crossover cable.

Pin

DCE Signal Name

Input/Output

1

2 Receive

Data

RD Output

1

2

3

4

5

6

7

8

9

3 Transmit

Data TD

Input

4

Data Terminal Ready DTR

Input

5

Signal Ground

6

Data Set Ready

DSR

Output

7

Request to Send

RTS

Input

8

Clear to Send

CTS

Output

Branch Circuit Protection

Always disconnect the power supply cord before opening to avoid electrical shock.
Afin d’éviter les chocs électriques, débranchez le cable électrique avant d’ouvrir.
Immer Netzleitung auskuppeln vor den Aufmachen um elektrischen Schlag zu vermeiden.

Cabinet Distribution Units feature Branch Circuit protection on all outlets in the form of internal fuses. These
fuses meet the strict safety requirements of UL/CSA 60950-1 for Branch Circuit Protection.

Time-Delay Fuses – Class G

Amperes Bussman

Part

Number

20 SC-20

CooperBussman product data-sheet #1024

Advertising