Snmp traps, Advanced operations – American Power Conversion AmpMeter PDU User Manual

Page 38

Advertising
background image

4. Advanced Operations

Displaying SNMP configuration information

The Show SNMP command displays all SNMP configuration information.

SNMP support status

SNMP community strings

Trap timer value

• Trap

destinations

To display SNMP configuration information:

At the AmpMeter PDU: prompt, type

show snmp

and press

Enter

.

Example

The following command displays the SNMP configuration information:

AmpMeter PDU: show snmp<Enter>
SNMP Configuration
SNMP: Enabled
SET Community String: private
GET Community String: public
TRAP Community String: trap
Error Trap Repeat Time (seconds): 180
Trap Destination 1: 64.42.31.208
Trap Destination 2: (undefined)

SNMP Traps

The AmpMeter PDU supports three types of SNMP traps. Traps are enabled at the tower (T), infeed (I) or
outlet (O) level.

Trap Summary

Name Level(s) Description

Status

T, I, O

Operational status change

Change

O

Control status change

Load

I

Input load out of limit

All traps include the Location of the AmpMeter PDU as defined with the Set Location command. See Creating a
location description on page 12 for more information.

Status trap

A Status trap is generated when an error condition occurs on a tower, infeed or outlet. Status traps include the
reported Status, the Location of the AmpMeter PDU, and identifier and name of the affected tower, infeed or
outlet.

Any Trap Status generates a Status trap and triggers the trap timer. A new trap is generated at the end of
every timer period until the Status returns to a non-error status.

Tower Status traps

Status Error Description

Normal

Tower is working correctly

NoComm

x

Communication to the tower has been lost

Infeed Status traps

Status Error Description

On

Infeed is on

OffError

x

Infeed should be on but no current is sensed at the infeed

NoComm

x

Communication to the infeed has been lost

Page 38 - 301-0399-3 Rev A.