4. Advanced Operations

Setting the Temperature sensor threshold limits

The Set Trap THS Templow and Set Trap THS Temphigh commands are used to set the lower and upper
threshold limits for the Temperature sensor.

To set the Temperature threshold limits:

At the AmpMeter PDU: prompt, type

set trap ths

,

templow

or

temphigh

, followed by the sensor name and

a value from 0 to 127 in degrees Celsius. Press

Enter

.

Example

The following command sets the second temperature high threshold limit to 95:

AmpMeter PDU: set trap ths temphigh .a2 95<Enter>

Enabling or Disabling the Humid trap

The Set Trap THS Humid command is used to enable or disable the Humid trap.

To Enable or Disable the Humid trap:

At the AmpMeter PDU: prompt, type

set trap ths humid

, followed by the sensor name and

on

or

off

. Press

Enter

.

Example

The following command enables the Humid trap for the first temperature-humidity sensor:

AmpMeter PDU: set traps ths humid .a1 on<Enter>

Setting the Humidity sensor threshold limits

The Set Trap THS Humidlow and Set Trap THS Humidhigh commands are used to set the lower and upper
threshold limits for the Humidity sensor.

To set the Humidity threshold limits:

At the AmpMeter PDU: prompt, type

set trap ths

,

humidlow

or

humidhigh

, followed by the sensor name

and a value from 0 to 100 in percent relative humidity. Press

Enter

.

Example

The following command sets the first humidity sensor low threshold limit to 5:

AmpMeter PDU: set trap ths humidlow .a1 5<Enter>