Bryant 607C-A User Manual

Page 24

Advertising
background image

24

OF2

OF1

ON

QUIET

SHIFT

120

30

60

60

30

90

INTER

V

AL

TIMER

OFF

P3

DFT

O R

W

2

Y C

T2 C C O

DFT

T1

Y

P1

J1

SPEEDUP

Speedup
Pins

Defrost interval
DIP switches

Quiet
Shift

A08020

Fig. 19 -- Defrost Control

Step 3 — Outdoor Fan

Keep the condenser fan free from all obstructions to ensure
proper cooling operation. Never place articles on top of the

unit. Damage to unit may result.

1. Remove 6 screws holding outdoor grille and motor to top

cover.

2. Turn motor/grille assembly upside down on top cover to

expose fan blade.

3. Inspect the fan blades for cracks or bends.
4. If fan needs to be removed, loosen setscrew and slide fan off

motor shaft.

5. When replacing fan blade, position blade back to same posi-

tion as before.

6. Ensure that setscrew engages the flat area on the motor shaft

when tightening.

7. Replace grille.

Step 4 — Electrical Controls and Wiring

Inspect and check the electrical controls and wiring annually. Be

sure to turn off the electrical power to the unit.
Remove access panels (see Fig 22) to locate all the electrical

controls and wiring. Check all electrical connections for tightness.
Tighten all screw connections. If any discolored or burned

connections are noticed, disassemble the connection, clean all the

parts, restrip the wire end and reassemble the connection properly
and securely.
After inspecting the electrical controls and wiring, replace all the
panels. Start the unit, and observe at least one complete cooling

cycle to ensure proper operation. If discrepancies are observed in
operating cycle, or if a suspected malfunction has occurred, check

each

electrical

component

with

the

proper

electrical

instrumentation. Refer to the unit wiring label when making these

checkouts.

Step 5 — Refrigerant Circuit

Inspect all refrigerant tubing connections and the unit base for oil
accumulation annually. Detecting oil generally indicates a

refrigerant leak.
If oil is detected or if low performance is suspected, leak--test all

refrigerant tubing using an electronic leak detector, or liquid--soap

solution. If a refrigerant leak is detected, refer to Check for
Refrigerant Leaks section.
If no refrigerant leaks are found and low performance is suspected,
refer to Checking and Adjusting Refrigerant Charge section.

Step 6 — Indoor Airflow

The heating and/or cooling airflow does not require checking

unless improper performance is suspected. If a problem exists, be
sure that all supply--air and return--air grilles are open and free

from obstructions, and that the air filter is clean. When necessary,
refer to Indoor Airflow and Airflow Adjustments section to check

the system airflow.

Step 7 — Metering Devices--TXV & Piston

This unit uses 2 types of metering devices. The outdoor metering
device is a fixed orifice and is contained in the brass hex--body in

each liquid line feeding the outdoor coils. The indoor metering
device is a TXV type device.

607C

--

--

A

Advertising