Operation, 607c -- -- a – Bryant 607C-A User Manual

Page 47

Advertising
background image

47

Table 16 – CO

2

Sensor Standard Settings

SETTING

EQUIPMENT

OUTPUT

VENTILATION

RATE

(CFM/

PERSON)

ANALOG

OUTPUT

CO

2

CONTROL

RANGE

(PPM)

OPTIONAL

RELAY

SETPOINT

(PPM)

RELAY

HYSTERESIS

(PPM)

1

Proportional

Any

0---10V

4---20mA

0---2000

1000

50

2

Interface w/Standard Building

Control System

Proportional

Any

2---10V

7---20mA

0---2000

1000

50

3

Exponential

Any

0---10V

4---20mA

0---2000

1100

50

4

Proportional

15

0---10V

4---20mA

0---1100

1100

50

5

Economizer

Proportional

20

0---10V

4---20mA

0---900

900

50

6

Exponential

15

0---10V

4---20mA

1---1100

1100

50

7

Exponential

20

0---10V

4---20mA

0---900

900

50

8

Health & Safety

Proportional

---

0---10V

4---20mA

0---9999

5000

500

9

Parking/Air Intakes/Loading Docks

Proportional

---

0---10V

4---20mA

0---2000

700

50

Table 17 – CO

2

Sensor Standard Settings Economizer Input/Output Logic

INPUTS

OUTPUTS

DEMAND

CONTROL

VENTILATION

(DCV)

ENTHALPY

Y1

Y2

COMPRESSOR

N TERMINAL

OUTDOOR

RETURN

STAGE

1

STAGE

2

OCCUPIED

UNOCCUPIED

DAMPER

Below set (DCV

LED Off)

High (Free Cooling

LED off)

Low

On

On

On

On

Minimum position

Closed

On

Off

On

Off

Off

Off

Off

Off

Low (Free Cooling

LED on)

High

On

On

On

Off

Modulating** (between min.

position and full---open)

Modulating** (between closed

and full---open)

On

Off

Off

Off

Off

Off

Off

Off

Minimum position

Closed

Above set (DCV

LED On)

High (Free Cooling

LED off)

Low

On

On

On

On

Modulating{{ (between

min. position and DCV

maximum)

Modulating{{ (between closed

and DCV maximum)

On

Off

On

Off

Off

Off

Off

Off

Low (Free Cooling

LED on)

High

On

On

On

Off

Modulating***

Modulating{{{

On

Off

Off

Off

Off

Off

Off

Off

* For single enthalpy control, the module compares outdoor enthalpy to the ABCD set point.

{

Power at N terminal determines Occupied/Unoccupied setting: 24 vac (Occupied), now power (Unoccupied).

**Modulating is based on the supply--- air sensor signal.

{{

Modulation is based on the DCV signal.

***Modulation is based on the greater of DCV and supply--- air sensor signals, between minimum position and either maximum position (DCV) or fully open (supply--- air signal).

{{{

Modulating is based on the greater of DCV and supply--- air sensor signals, between closed and wither maximum position (DCV) or fully open (supply--- air signal).

OPERATION

Sequence of Operation—When free cooling is not available, the
compressor will be controlled by the thermostat. When free cooling
is available, the outdoor--air damper is modulated by the Economizer
control to provide a 50_ to 55_F (10_ to 12.8_C) supply--air
temperature into the zone. As the supply--air temperature fluctuates
above 55_ (12.8_C) or below 50_F (10_C), the dampers will be
modulated (open or close) to bring the supply--air temperature back
within the set points. For Economizer operation, there must be a
thermostat call for the fan (G). This will move the damper to its
minimum position during the occupied mode.
NOTE: The DCV Max potentiometer must be closed (CCW)
when not using CO

2

sensor.

Above 50_F (10_C) supply--air temperature, the dampers will
modulate from 100% open to the minimum open position. From

50_F to 45_F (10_ to 7.2_C) supply--air temperature, the dampers
will maintain at the minimum open position. Below 45_F (7.2_C),

the dampers will be completely shut. As the supply--air temperature

rises, the dampers will come back open to the minimum open
position once the supply--air temperature rises to 48_F (8.9_C). If

power exhaust is installed, as the outdoor--air damper opens and
closes, the power exhaust fans will be energized and deenergized.

If field--installed accessory CO

2

sensors are connected to the

Economizer control, a demand controlled ventilation strategy will

begin to operate. As the CO

2

level in the zone increases above the

CO

2

set point, the minimum position of the damper will be

increased proportionally. As the CO

2

level decreases because of the

increase in fresh air, the outdoor--air damper will be proportionally
closed. Damper position will follow the higher demand condition

from DCV mode or free cooling mode. Damper movement from

full closed to full open (or vice versa) will take between 1 1/2 and
2 1/2 minutes. If free cooling can be used as determined from the

appropriate changeover command (dry bulb, enthalpy curve, or
differential enthalpy), a call for cooling (Y1 closes at the

thermostat) will cause the control to modulate the dampers open to

maintain the supply air temperature set point at 50_ to 55_F (10_
to 12.8_C). As the supply air temperature drops below the set point

range of 50_ to 55_F (10_ to 12.8_C), the control will modulate
the outdoor--air dampers closed to maintain the proper supply--air

temperature.