Warning – Bryant 607C-A User Manual

Page 34

Advertising
background image

34

Large Chassis

To install the Vertical Economizer on the large chassis perform the

following procedure:

1. Turn off unit power supply and install lockout tag.

ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal

injury or death.
Before installing or servicing system, always turn off main

power to system and install lockout tag. There may be more

than one disconnect switch. Turn off accessory heater

power switch if applicable.

!

WARNING

2. Remove economizer hood top panel from the return side of

the unit. See Fig. 30. Keep screws and panel next to the
unit.

3. Remove red shipping tape that attaches the outside air

temperature (OAT) sensor to the economizer assembly and
place sensor next to the unit.

4. Remove horizontal return duct cover panel and cut the wire

ties that hold the hood divider to the economizer assembly.
Slide hood divider off from the two slots holding it in place

and place next to the unit. See Fig. 31.

5. Replace horizontal return duct cover panel. Screw in place

ensuring all seams are air and watertight.

6. Open economizer hood package found on the top skid.

Mount OAT sensor to its assigned bracket by screwing
together with provided two #8 fasteners. Afterwards install
OAT sensor to the right side hood panel with the provided

#10 screws. See Fig. 32.

7. Install the 2 angle filter brackets to the right and left hood

side panels respectively with the #10 screws provided. See

Fig. 33.

8. Assemble hood according to Fig. 34 screwing together

with provided #10 sheet metal screws.

9. Install assembled hood over the economizer opening in the

replacement return chamber panel. See Fig. 35. Screw in

place through pre-punched holes. Make sure all seams are
air and watertight.

NOTE: The two wires that connect to the outside air temperature
sensor (OAT) should remain accessible.

10. Connect the outside air temperature sensor (OAT) to the

economizer per wiring diagram.

OAT Sensor

Filter Access
Panel

Hoop Top
Panel

A09696

Fig. 30 -- Economizer Hood Top Panel Removal

Horizontal
Return Duct
Cover Panel

Hood
Divider

Hood Divider
(Removed)

A09697

Fig. 31 -- Horizontal Return Duct Cover Panel and Hood Divider Removal

607C

--

--

A