Right Hood
Side Panel

Hood Top Panel

Left Hood
Side Panel

Hood
Divider

A09700

Fig. 34 -- Hood Assembly

A09701

Fig. 35 -- Economizer Hood Installation

11. Open the filter clips on the inside of the hood top. Insert the

aluminum filter into the hood and close the clips to hold in
place. See Fig. 36.

12. To replace air filters, open filter access door remove old

filters and install new disposable filters in filter rack. See

Table 14 for filter part numbers.

IMPORTANT: On the the bent coil (See Fig. 37 to determine coil
type) filter rack, the 18 x 24 x 1 (257.2mm x 609.6mm x25.4mm)
filter must be installed through the filter access door first then
install the 16 x 24 x 1 (406.4mm x 609.6mm x 25.4mm) filter.

NOTE:

The economizer control settings and the filters are

accessible through the filter access door.

Table 14 – Filter Part Number

DESCRIPTION

PART NUMBER

Straight Indoor

Coil Air Filter

14 x 24 x 1

(355.6 x 609.6 x 25.4 mm)

KH01AA314

16 x 24 x 1

(406.4 x 609.6 x 25.4 mm)

KH01AA316

Bent Indoor

Coil Air Filter

16 x 24 x 1

(406.4 x 609.6 x 25.4 mm)

KH01AA316

18 x 24 x 1

(457.2 x 609.5 x 25.4 mm)

KH01AA318

13. Economizer controls are set to a standard factory setting.

Nevertheless, you can adjust these settings through the filter

access door. Review the settings in the Operation section:

(1.) The standard economizer controller has a factory

setting of “C” for the outdoor air temperature

changeover and 63_F (17_C) for the supply air
(mixed air) temperature sensor. The outdoor air

temperature changeover setting is adjusted on the
sensor by setting the dip switches on the sensor.
The ABCD potentiometer on the economizer

control should be set to the “D” position.

(2.) The low ambient compressor lockout switch setting

is fixed at 42_F (5.6_C).

(3.) The minimum position for the outdoor air damper

can be configured at the controller. When not using
a CO

2

sensor, the DCV Max potentiometer must be

completely closed (CCS) for the Minimum Posi-

tion potentiometer to function correctly.

(4.) Settings for the optional outdoor enthalpy sensor,

indoor enthalpy sensor, and CO

2

sensor can also be

configured at the controller.

14. Replace the filter access panel. Screw in place ensuring all

seams are air and watertight.

15. Install all economizer accessories then power HVAC unit

and test cycle economizer.