CONFIGURATION

Economizer Standard Sensors

OUTDOOR AIR TEMPERATURE (OAT) SENSOR— The
outdoor air temperature sensor (HH57AC080) is a 10 to 20mA
device used to measure the outdoor--air temperature. The outdoor--air
temperature is used to determine when the Economizer can be used
for free cooling. The operating range of temperature measurement is
40 to 100_F (4.4 to 37.8_C). The sensor has 8 selectable temperature
changeover setpoints. The temperature changeover is set using 3 dip
switches on the sensor. The ABCD potentiometer on the controller
should be set to the “D” position. See Fig. 40.
SUPPLY AIR TEMPERATURE (SAT) SENSOR—The supply
air temperature sensor is a 3 KΩ thermistor located at the inlet of the
indoor fan. See Fig. 38. The operating range of temperature
measurement is 0_ to 158_F (--17.8_ to 70_C). See Table 15 for
sensor temperature/resistance values. The temperature sensor looks
like an eyelet terminal with wires running to it. The sensor is located
in the “crimp end” and is sealed from moisture.

Table 15 – Supply Air Sensor Temperature/Resistance Values

TEMPERATURE

(_F)

CELSIUS (_C)

RESISTANCE (OHMS)

---22

---30

53,010

---4

---20

29,091

14

---10

16,590

32

0

9,795

50

10

5,970

68

20

3,747

77

25

3,000

86

30

2,416

104

40

1,597

122

50

1,080

140

60

746

158

70

525

Indoor
Blower

Supply Air Temperature
Sensor (SAT)

A09707

Fig. 38 -- SAT Location