Caution, Warning, Step 6 — provide for condensate disposal – Bryant 607C-A User Manual

Page 8: Step 7 — install electrical connections

Advertising
background image

8

3. Use flexible transition between rigid ductwork and unit to

prevent transmission of vibration. The transition may be

screwed or bolted to duct flanges. Use suitable gaskets to
ensure weather--tight and airtight seal.

4. All units must have field--supplied filters or accessory filter

rack installed in the return--air side of the unit.
Recommended sizes for filters are shown in Table 1.

5. Size all ductwork for maximum required airflow (either

heating or cooling) for unit being installed. Avoid abrupt
duct size increases or decreases or performance may be

affected.

6. Adequately insulate and weatherproof all ductwork located

outdoors. Insulate ducts passing through unconditioned
space, and use vapor barrier in accordance with latest issue
of Sheet Metal and Air Conditioning Contractors National

Association (SMACNA) and Air Conditioning Contractors
of America (ACCA) minimum installation standards for

heating and air conditioning systems. Secure all ducts to
building structure.

7. Flash, weatherproof, and vibration--isolate all openings in

building structure in accordance with local codes and good
building practices.

Step 6 — Provide for Condensate Disposal

NOTE: Ensure that condensate--water disposal methods comply
with local codes, restrictions, and practices.
The 607----A units dispose of condensate through a 3/4 in. NPT
female fitting that exits on the compressor end of the unit.

Condensate water can be drained directly onto the roof in rooftop
installations (where permitted) or onto a gravel apron in ground

level installations. Install a field--supplied condensate trap at end of
condensate connection to ensure proper drainage. Make sure that

the outlet of the trap is at least 1 in. (25 mm) lower than the

drain--pan condensate connection to prevent the pan from
overflowing. Prime the trap with water. When using a gravel apron,

make sure it slopes away from the unit.
If the installation requires draining the condensate water away from

the unit, install a field--supplied 2 --in. (51mm) trap at the

condensate connection to ensure proper drainage. Condensate trap
is available as an accessory or is field--supplied. Make sure that the

outlet of the trap is at least 1 in. (25 mm) lower than the unit
drain--pan condensate connection to prevent the pan from

overflowing. Connect a drain tube using a minimum of
field--supplied 3/4--in. PVC or field--supplied 3/4--in. copper pipe

at outlet end of the 2--in. (51 mm) trap. (See Fig. 11) Do not

undersize the tube. Pitch the drain tube downward at a slope of at
least 1 in. (25 mm) every 10 ft (3 m) of horizontal run. Be sure to

check the drain trough for leaks. Prime the trap at the beginning of
the cooling season start--up.

A

B

C

MAXIMUM ALLOWABLE

DIFFERENCE in. (mm)

A-C

1/4

1/4

1/4

(6.35)

(6.35)

(6.35)

A-B

B-C

A07925

Fig. 7 -- Unit Leveling Tolerances

OPTIONAL

RETURN

AIR

OPENING

OPTIONAL

SUPPLY

AIR

OPENING

EVAP. COIL

COND. COIL

(50.8mm)

A07926

Fig. 8 -- Slab Mounting Detail

Step 7 — Install Electrical Connections

UNIT COMPONENT DAMAGE HAZARD
Failure to follow this caution may result in damage to the unit

being installed.

1. Make all electrical connections in accordance with NEC

NFPA 70 (latest edition) and local electrical codes
governing such wiring. In Canada, all electrical

connections must be in accordance with CSA standard
C22.1 Canadian Electrical Code Part 1 and applicable
local codes. Refer to unit wiring diagram.

2. Use only copper conductor for connections between

field--supplied electrical disconnect switch and unit. DO

NOT USE ALUMINUM WIRE.

3. Be sure that high--voltage power to unit is within

operating voltage range indicated on unit rating plate. On

3--phase units, ensure phases are balanced within 2
percent. Consult local power company for correction of

improper voltage and/or phase imbalance.

4. Do not damage internal components when drilling

through any panel to mount electrical hardware, conduit,
etc.

!

CAUTION

ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury

or death.
The unit cabinet must have an uninterrupted, unbroken

electrical ground. This ground may consist of an electrical

wire connected to the unit ground screw in the control

compartment, or conduit approved for electrical ground when

installed in accordance with NEC,NFPA 70 National Fire

Protection Association (latest edition) (in Canada, Canadian

Electrical Code CSA C22.1) and local electrical codes.

!

WARNING

High--Voltage Connections

The unit must have a separate electrical service with a
field--supplied, waterproof disconnect switch mounted at, or within

sight from the unit. Refer to the unit rating plate, NEC and local
codes for maximum fuse/circuit breaker size and minimum circuit

amps (ampacity) for wire sizing.
The field--supplied disconnect may be mounted on the unit over
the high--voltage inlet hole when the standard power and

low--voltage entry points are used. See Fig. 2 and 3 for acceptable
location. Remove high voltage knockout.
See unit wiring label (Fig. 12--14) and Fig. 9 for reference when

making high voltage connections. Proceed as follows to complete
the high--voltage connections to the unit.

607C

--

--

A

Advertising