OAT Sensor

Hood Top
Panel

A09689

Fig. 23 -- Economizer Hood Top Panel Removal

OAT Sensor

A09690

Fig. 24 -- Oat Sensor Installed

6. Replace horizontal return duct cover panel. Screw in place

ensuring all seams are air and watertight.

7. Install the 2 angle filter brackets to the right and left hood

side panels respectively with the #10 screws provided. See
Fig. 26.

8. Assemble hood according to Fig. 27 screwing together with

provided #10 sheet metal screws.

9. Install assembled hood over the economizer opening in the

replacement return chamber panel. See Fig. 28. Screw in
place through pre-punched holes. Make sure all seams are

air and watertight.

NOTE: The two wires that connect to the outside air temperature
sensor (OAT) should remain accessible.

10. Connect the outside air temperature sensor (OAT) to the

economizer per wiring diagram.

11. Open the filter clips on the inside of the hood top. Insert the

aluminum filter into the hood and close the clips to hold in

place. See Fig. 29.

12. To replace 12 x 20 x1 (304.8mm x 508mm x 25.4mm) air

filters, open the filter access door (horizontal return duct

cover panel), remove old filters and install new disposable
filters in filter rack. See Table 13 for filter part number.

Table 13 – Filter Part Number

DESCRIPTION

PART NUMBER

Indoor Coil Air Filter

12 x 20 x 1

(304.8 x 508 x 25.4 mm)

KH01AA312

NOTE:

The economizer control settings and the filters are

accessible through the filter access door.

13. Economizer controls are set to a standard factory setting.

Nevertheless, you can adjust these settings through the filter
access door. Review the settings in the Operation section:

(5.) The standard economizer controller has a factory

setting of “C” for the outdoor air temperature

changeover and 63_F (17_C) for the supply air
(mixed air) temperature sensor. The outdoor air

temperature changeover setting is adjusted on the
sensor by setting the dip switches on the sensor.
The ABCD potentiometer on the economizer

control should be set to the “D” position.

(6.) The low ambient compressor lockout switch setting

is fixed at 42_F (5.6_C).

(7.) The minimum position for the outdoor air damper

can be configured at the controller. When not using

a CO

2

sensor, the DCV Max potentiometer must be

completely closed (CCW) for the Minimum Posi-

tion potentiometer to function correctly.

(8.) Settings for the optional outdoor enthalpy sensor,

indoor enthalpy sensor, and CO

2

sensor can also be

configured at the controller.

14. Replace the filter access panel. Screw in place ensuring all

seams are air and watertight.

15. Install all economizer accessories then power HVAC unit

and test cycle economizer.