26

Compressor Oil

The Copeland scroll compressor uses 3MAF POE oil. If additional

oil is needed, use Uniqema RL32--3MAF. If this oil is not
available, use Copeland Ultra 32 CC or Mobil Arctic EAL22 CC.

This oil is extremely hygroscopic, meaning it absorbs water
readily. POE oils can absorb 15 times as much water as other oils

designed to HCFC and CFC refrigerants. Take all necessary
precautions to avoid exposure of the oil to the atmosphere.

Servicing Systems on Roofs with Synthetic Materials

POE (polyolester) compressor lubricants are known to cause long

term damage to some synthetic roofing materials. Exposure, even if
immediately cleaned up, may cause embrittlement (leading to

cracking) to occur in one year or more. When performing any

service that may risk exposure of compressor oil to the roof, take
appropriate precautions to protect roofing. Procedures which risk

oil leakage include, but are not limited to, compressor replacement,
repairing refrigerant leaks, replacing refrigerant components such

as filter drier, pressure switch, metering device, coil, accumulator,

or reversing valve.
Synthetic Roof Precautionary Procedure

1. Cover extended roof working area with an impermeable

polyethylene (plastic) drip cloth or tarp. Cover an
approximate 10x10 ft (3x3 m) area.

2. Cover area in front of the unit service panel with a terry

cloth shop towel to absorb lubricant spills and prevent
run--offs, and protect drop cloth from tears caused by tools

or components.

3. Place terry cloth shop towel inside unit immediately under

component(s) to be serviced and prevent lubricant run--offs
through the louvered openings in the unit base.

4. Perform required service.
5. Remove and dispose of any oil contaminated material per

local codes.

Liquid Line Filter Drier

The biflow filter drier is specifically designed to operate with

Puron. Use only factory--authorized components. Filter drier must
be replaced whenever the refrigerant system is opened. When

removing a filter drier, use a tubing cutter to cut the drier from the
system. Do not unsweat a filter drier from the system. Heat from

unsweating will release moisture and contaminants from drier into

system.

Puron (R--410A) Refrigerant Charging

Refer to unit information plate and charging chart. Some R--410A

refrigerant cylinders contain a dip tube to allow liquid refrigerant to
flow from cylinder in upright position. For cylinders equipped

with a dip tube, charge Puron units with cylinder in upright

position and a commercial metering device in manifold hose.
Charge refrigerant into suction--line.

Step 13 — System Information

Loss of Charge Switch

The loss of charge switch is a protective device wired into control

circuit (low voltage). It shuts off the compressor if abnormally low
pressures are present in the refrigeration circuit.
NOTE:

Because these switches are attached to refrigeration

system under pressure, it is not advisable to remove this device for
troubleshooting unless you are reasonably certain that a problem
exists. If switch must be removed, remove and recover all system
charge so that pressure gauges read 0 psi. Never open system
without breaking vacuum with dry nitrogen.

Check Defrost Thermostat

The defrost thermostat is usually located on the lowest liquid

leaving circuit of the left condenser coil (see Fig. 22). The
thermostat closes at 32_F (0_C) and opens at 65_F (18_C).
The defrost thermostat signals heat pump that conditions are right
for defrost or that conditions have changed to terminate defrost. It

is a thermally actuated switch clamped to outdoor coil to sense its
temperature. Normal temperature range is closed at 32_  3_F (0
 1.7_C) and open at 65_  5_F (18  2.8_C).
NOTE: The defrost thermostat must be located on the liquid side
of the outdoor coil on the bottom circuit and as close to the coil as
possible.

FEEDER TUBE

STUB TUBE

DEFROST

THERMOSTAT

C99029

Fig. 22 -- Defrost Thermostat

TROUBLESHOOTING

Refer to the Cooling and Heating Troubleshooting Chart (Table 9)

for troubleshooting information.

START--UP CHECKLIST

Use the Start--Up Checklist.