Single phase units:

1. Run the high--voltage (L1, L2) and ground lead into the

control box.

2. Connect ground lead to chassis ground connection.
3. Locate the black and yellow wires connected to the line side

of the contactor.

4. Connect field L1 to black wire on connection 11 of the

compressor contactor.

5. Connect field wire L2 to yellow wire on connection 23 of

the compressor contactor.

POWER
SUPPLY

FIELD-SUPPLIED
FUSED DISCONNECT

HIGH VOLTAGE
POWER LEADS
(SEE UNIT WIRING
LABEL)

EQUIP GR

CONTROL BOX

LOW-VOLTAGE
POWER LEADS
(SEE UNIT
WIRING LABEL

)

W1

Y

G

R

C

WHT(W1)

YEL(Y)

GRN(G)

RED(R)

BRN(C)

THERMOSTAT
(TYPICAL)

ORN(O)

3-PHASE SHOWN
1-PHASE USES
TWO POWER
LEADS

W2

VIO (W2)

O

SPLICE BOX

DH

BLU(DH)

3-Phase
Only

GRA(Y2)

A09071

Fig. 9 -- High-- and Control--Voltage Connections

Three--phase units:

1. Run the high--voltage (L1, L2, L3) and ground lead into the

control box.

2. Connect ground lead to chassis ground connection.
3. Locate the black and yellow wires connected to the line side

of the contactor.

4. Connect field L1 to black wire on connection 11 of the

compressor contactor.

5. Connect field wire L3 to yellow wire on connection 13 of

the compressor contactor.

6. Connect field wire L2 to blue wire from compressor.

Special Procedures for 208--V Operation

ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal

injury or death.
Before installing or servicing system, always turn off main

power to system and install lockout tag. With disconnect

switch open, move black wire from transformer (3/16 in.)

terminal marked 230 to terminal marked 208. This retaps

transformer to primary voltage of 208 vac.

!

WARNING

Control Voltage Connections

NOTE: Do not use any type of power--stealing thermostat. Unit
control problems may result.

Use no. 18 American Wire Gage (AWG) color--coded, insulated
(35°C minimum) wires to make the control voltage connections

between the thermostat and the unit. If the thermostat is located
more than 100 ft (30.5 m) from the unit (as measured along the

control voltage wires), use no. 16 AWG color--coded, insulated

(35° C minimum) wires.

Standard Connections

Locate the eight (nine on 3--phase) low voltage thermostat leads in

24 volt splice box. See Fig. 9 for connection diagram. Run the

low--voltage leads from the thermostat, through the control wiring
inlet hole grommet (Fig. 2 and 3), and into the low--voltage splice

box. Provide a drip loop before running wires through panel.
Secure and strain relief all wires so that they do not interfere with

operation of unit. A gray wire is standard on 3--phase units for

connection to an economizer.
If an accessory electric heater is installed, low voltage leads from

heater must be connected to factory supplied control leads from
Indoor Fan Board P4 connector. Factory wires are provided for

electric heat staging W1 and W2 (W2 and W3 on IFB). If room
thermostat has only one stage of supplemental heat, connect white

and violet wires shown in Fig. 9 to second stage heat field wire.
Some electric heaters have four control wires (plus common wire).
Consult unit wiring diagram and electric heater wiring diagram for

additional details.

Transformer Protection

The transformer is of the energy--limiting type. It is set to withstand
a 30--second overload or shorted secondary condition. If an

overload or short is present, correct overload condition and check
for blown fuse on Interface Fan Board. Replace fuse as required

with correct size and rating.

Accessory Electric Heaters Installation

Electric heaters may be installed with the 607----A units per
instructions supplied with electric heater package. See unit rating

plate for factory--approved electric heater kits.

Sequence of Operation

a. CONTINUOUS FAN

(1.) Thermostat closes circuit R to G energizing the

blower motor for continuous fan.

b. COOLING MODE

(1.) If indoor temperature is above temperature set

point, thermostat closes circuits R to G, R to Y and

R to O--The unit delivers cooling airflow.

c. ELECTRIC HEATING MODE

(1.) Thermostat closes circuit R to W/W1, or W2 and R

to G. There are no on or off delays.

d. HEAT PUMP HEATING MODE

(1.) Thermostat closes circuits R to G and R to Y. The

compressor, indoor and outdoor fans are energized.

e. HEAT PUMP HEATING WITH AUXILIARY

ELECTRIC HEAT

(1.) Thermostat closes circuits R to G, R to Y and R to

W/W1 or W2. The compressor, indoor and outdoor
fans are energized, as well as the electric heat

relays.

f. DEFROST MODE

The defrost mode is automatically energized by the

defrost board during heating mode. The defrost board
energizes “O” (reversing valve) and “W2” (electric

heat). It also de--energizes the outdoor fan. When defrost
is complete, unit will return to heating mode. If room

thermostat is satisfied during defrost, unit will shut
down and restart in defrost on next call for heat.