10

SEAL STRIP

HOOD TOP

SEAL STRIP

HOOD
SIDE

SCREEN
RETAINER

HOOD SIDE

SCREEN
TRACKS

OUTDOOR AIR INLET SCREEN

SEAL STRIP

OUTDOOR-AIR HOOD – UNASSEMBLED

HOOD SIDES AND TOP ASSEMBLED

TRACKS FOR AIR
INLET SCREEN

HOOD
SIDE

HOOD TOP

C07504

Fig. 9 -- Outdoor--Air Hood Details

Economizer Hood —
NOTE
: If the power exhaust accessory is to be installed
on the unit, the hood shipped with the unit will not be

used and must be discarded. Save the aluminum filter for
use in the power exhaust hood assembly.

1. The indoor coil access panel will be used as the top of

the hood. Remove the screws along the sides and bot-

tom of the indoor coil access panel. See Fig. 10.

2. Swing out indoor coil access panel and insert the

hood sides under the panel (hood top). Use the screws

provided to attach the hood sides to the hood top. Use

screws provided to attach the hood sides to the unit.

See Fig. 11.

3. Remove the shipping tape holding the economizer ba-

rometric relief damper in place.

4. Insert the hood divider between the hood sides. See

Fig. 11 and 12. Secure hood divider with 2 screws on

each hood side. The hood divider is also used as the

bottom filter rack for the aluminum filter.

5. Open the filter clips which are located underneath the

hood top. Insert the aluminum filter into the bottom

filter rack (hood divider). Push the filter into position

past the open filter clips. Close the filter clips to lock

the filter into place. See Fig. 12.

6. Caulk the ends of the joint between the unit top panel

and the hood top.

7. Replace the filter access panel.

SIDE

PANEL

INDOOR

COIL

ACCESS

PANEL

INDOOR

COIL

ACCESS

PANEL

CAULK

HERE

TOP

SIDE

PANEL

C06025

Fig. 10 -- Indoor Coil Access Panel Relocation

B

TOP

PANEL

INDOOR COIL

ACCESS PANEL

19 1/16”

SCREW

HOOD DIVIDER

LEFT

HOOD

SIDE

33 3/8”

(848mm)

(483mm)

C06026

Fig. 11 -- Economizer Hood Construction

DIVIDER

BAROMETRIC

RELIEF

CLEANABLE

ALUMINUM

FILTER

FILTER

HOOD

FILTER

CLIP

OUTSIDE

AIR

C06027

Fig. 12 -- Economizer Filter Installation

551J

j