Caution – Bryant 551J User Manual

Page 8

Advertising
background image

8

A-B

0.5” (13)

B-C

1.0” (25)

A-C

1.0” (25)

MAXIMUM ALLOWABLE

DIFFERENCE IN. (MM)

C06110

Fig. 4 -- Unit Leveling Tolerances

Step 5 — Field Fabricate Ductwork

Cabinet return-air static pressure (a negative condition)

shall not exceed 0.35 in. wg (87 Pa) with economizer or

0.45 in. wg (112 Pa) without economizer.

For vertical ducted applications, secure all ducts to roof

curb and building structure on vertical ducted units. Do
not connect ductwork to unit.

Insulate and weatherproof all external ductwork, joints,

and roof openings with counter flashing and mastic in

accordance with applicable codes.

Ducts passing through unconditioned spaces must be

insulated and covered with a vapor barrier.

If a plenum return is used on a vertical unit, the return

should be ducted through the roof deck to comply with

applicable fire codes.

For units with accessory electric heaters: Horizontal

applications require a minimum clearance to combustible

surfaces of 1--in (25 mm) from duct for first 12--in (305 mm)

away from unit. Vertical applications do not require a

minimum clearance around ductwork.

Step 6 — Rig and Place Unit

Keep unit upright and do not drop. Spreader bars are not

required if top crating is left on unit. Rollers may be used

to move unit across a roof. Level by using unit frame as a

reference. See Table 1 and Fig. 5 for additional

information.

Lifting holes are provided in base rails as shown in Fig. 5.

Refer to rigging instructions on unit.

Before setting the unit onto the curb, recheck gasketing on

curb.

UNIT DAMAGE HAZARD
Failure to follow this caution may result in

equipment damage.
All panels must be in place when rigging. Unit is not

designed for handling by fork truck.
If using top crate as spreader bar, once unit is set,

carefully lower wooden crate off building roof top to

ground. Ensure that no people or obstructions are

below prior to lowering the crate.

CAUTION

!

C06005

UNIT

MAX WEIGHT

DIMENSIONS

A

B

C

LB

KG

IN

MM

IN

MM

IN

MM

551J*04A

700

318

74.5

1890

36.5

925

33.5

850

551J*05A

830

377

74.5

1890

36.5

925

41.5

1055

551J*06A

865

393

74.5

1890

36.0

915

41.5

1055

NOTES:

1. Dimensions in ( ) are in millimeters.
2. Hook rigging shackles through holes in base rail, as shown in detail “A.” Holes in base rails are centered around the

unit center of gravity. Use wooden top to prevent rigging straps from damaging unit.

Fig. 5 -- Rigging Details