Positioning on Curb —

Position unit on roof curb so that the following clearances

are maintained:

1

/

4

in. (6.4 mm) clearance between the

roof curb and the base rail inside the front and rear, 0.0 in.

clearance between the roof curb and the base rail inside on

the duct end of the unit. This will result in the distance

between the roof curb and the base rail inside on the

condenser end of the unit being approximately equal to

Fig. 3, section C--C.

Although unit is weatherproof, guard against water from

higher level runoff and overhangs.

UNIT DAMAGE HAZARD
Failure to follow this caution may result in

equipment damage.
All panels must be in place when rigging. Unit is not

designed for handling by fork truck.

CAUTION

!

After unit is in position, remove rigging skids and

shipping materials.

Step 7 — Convert to Horizontal and Connect

Ductwork (when required)

Unit is shipped in the vertical duct configuration. Unit

without factory--installed economizer or return air smoke

detector option may be field--converted to horizontal ducted

configuration. To convert to horizontal configuration,

remove screws from side duct opening covers and remove

covers. Using the same screws, install covers on vertical

duct openings with the insulation--side down. Seals around

duct openings must be tight. See Fig. 6.

C06108

Fig. 6 -- Horizontal Conversion Panels

Field--supplied flanges should be attached to horizontal

duct openings and all ductwork should be secured to the

flanges. Insulate and weatherproof all external ductwork,

joints, and roof or building openings with counter flashing

and mastic in accordance with applicable codes.

Do not cover or obscure visibility to the unit’s informative

data plate when insulating horizontal ductwork.

Step 8 — Install Outside Air Hood

The outdoor hood components are shipped in a box

located in the unit return air compartment behind the

outdoor--ar opening access panel (or economizer). Access

is through the filter access panel. See Fig. 7.

FILTER ACCESS PANEL

OUTDOOR-AIR OPENING AND

INDOOR COIL ACCESS PANEL

COMPRESSOR

ACCESS PANEL

C06023

Fig. 7 -- Typical Access Panel Locations

1. To remove the existing unit filter access panel, raise

the panel and swing the bottom outward. The panel is

now disengaged from the track and can be removed.

2. To remove the component box from its shipping posi-

tion, remove the screw holding the hood box bracket

to the top of the economizer. Slide the hood box out

of the unit. See Fig. 8.

Hood

Box

HOOD BOX

BRACKET

C06024

Fig. 8 -- Hood Box Removal

Motorized 2--Position Damper Hood —

1. Assemble outdoor--air hood top and side plates as

shown in Fig. 9. Install seal strips on hood top and

sides. Put aside screen retainer and screws for later

assembly.

2. Fasten hood top and side plate assembly to unit with

screws provided. See Fig. 9.

3. Slide outdoor--air inlet screen into screen track on

hood side plates. While holding screen) in place,

fasten screen retainer to hood using screws provided.

4. Replace filter access panel. See Fig. 7.