Completing Installation of Return Air Smoke

Sensor:

1. Unscrew the two screws holding the Return Air

Sensor detector plate. See Fig. 34. Save the screws.

2. Remove the Return Air Sensor and its detector plate.
3. Rotate the detector plate so the sensor is facing

outwards and the sampling tube connection is on the

bottom. See Fig. 35.

4. Screw the sensor and detector plate into its operating

position using screws from Step 1. Make sure the

sampling tube connection is on the bottom and the

exhaust tube is on the top. See Fig. 35.

5. Connect the flexible tube on the sampling inlet to the

sampling tube on the basepan.

Flexible
Exhaust Tubes

Screws

Sample Tube

C08126

Fig. 34 -- Return Air Detector Shipping Position

C08127

Fig. 35 -- Return Air Sensor Operating Position

Additional Application Data — Refer to Catalog No.

HKRNKA--1XA for discussions on additional control

features of these smoke detectors including multiple unit

coordination.