Bryant 551J User Manual

Page 22

Advertising
background image

22

Table 3 – RTU--MP Controller Inputs and Outputs

POINT NAME

BACnet OBJECT

NAME

TYPE OF I/O

CONNECTION PIN

NUMBERS

INPUTS

Space Temperature Sensor

sptsens

AI (10K Thermistor)

J20---1, 2

Supply Air Temperature

sat

AI (10K Thermistor)

J2---1, 2

Local Outside Air Temperature Sensor

oatsens

AI (10K Thermistor)

J2---3, 4

Space Temperature Offset Pot

sptopot

AI (100K Potentiometer)

J20---3

Indoor Air Quality

iaq

AI (4---20 ma)

J4---2, 3

Outdoor Air Quality

oaq

AI (4---20 ma)

J4---5, 6

Safety Chain Feedback

safety

DI (24 VAC)

J1---9

Compressor Safety

compstat

DI (24 VAC)

J1---2

Fire Shutdown

firedown

DI (24 VAC)

J1---10

Enthalpy Switch

enthalpy

DI (24 VAC)

J2---6, 7

Humidistat Input Status

humstat

DI (24 VAC)

J5---7, 8

CONFIGURABLE INPUTS*

Space Relative Humidity

sprh

AI (4---20 ma)

J4---2,3 or J4---5,6

Outside Air Relative Humidity

oarh

AI (4---20 ma)

Supply Fan Status

fanstat

DI (24 VAC)

J5---1,2 or J5---3,4 or

J5 5,6 or J5---7,8

Filter Status

filtstat

DI (24 VAC)

Remote Occupancy Input

remocc

DI (24 VAC)

OUTPUTS

Economizer Commanded Position

econocmd

4---20ma

J2---5

Supply Fan Relay State

sf

DO Relay (24VAC , 1A)

J1---4

Compressor 1 Relay State

comp_1

DO Relay (24VAC , 1A)

J1---8

Compressor 2 Relay State

comp_2

DO Relay (24VAC , 1A)

J1---7

Heat Stage 1 Relay State

heat_1

DO Relay (24VAC , 1A)

J1---6

Heat Stage 2 Relay State

heat_2

DO Relay (24VAC , 1A)

J1---5

Power Exhaust Relay State

aux_2

DO Relay (24VAC , 1A)

J11---3

Dehumidification Relay State

humizer

DO Relay (24VAC, 1A)

J11---7, 8

LEGEND

AI --- Analog Input

AO --- Analog Output

DI --- Discrete Input

DO --- Discrete Output

* These inputs (if installed) take the place of the default input on the specific channel according to schematic.
Parallel pins J5---1 = J2---6, J5---3 = J1---10, J5---5 = J1---2 are used for field---installation.

The RTU--MP controller requires the use of a Byrant

space sensor. A standard thermostat cannot be used with

the RTU--MP system.

Supply Air Temperature (SAT) Sensor -- On FIOP--equipped

551J unit, the unit is supplied with a supply--air temperature

(SAT) sensor (33ZCSENSAT). This sensor is a tubular probe

type, approx 6--inches (12.7 mm) in length. It is a nominal

10--k ohm thermistor.

The SAT is factory--wired. The SAT probe is wire--tied to

the supply--air opening (on the horizontal opening end) in

its shipping position. Remove the sensor for installation.

Re--position the sensor in the flange of the supply--air

opening or in the supply air duct (as required by local

codes). Drill or punch a

1

/

2

--in. hole in the flange or duct.

Use two field--supplied, self--drilling screws to secure the

sensor probe in a horizontal orientation. See Fig. 39.

SUPPLY AIR

RETURN AIR

SUPPLY AIR
TEMPERATURE
SENSOR

ROOF
CURB

C08200

Fig. 39 -- Typical Mounting Location for Supply Air

Temperature (SAT) Sensor on Small Rooftop Units

551J

j