Outdoor Air Temperature (OAT) Sensor -- The OAT is

factory--mounted

in

the

EconoMi$er2

(FIOP

or

accessory). It is a nominal 10k ohm thermistor attached to

an eyelet mounting ring.

EconoMi$er2 -- The RTU--MP control is used with

EconoMi$er2 (option or accessory) for outdoor air

management. The damper position is controlled directly

by the RTU--MP control; EconoMi$er2 has no internal

logic device.

Outdoor air management functions can be enhanced with

field--installation of these accessory control devices:

Enthalpy control (outdoor air or differential sensors)
Space CO

2

sensor

Outdoor air CO

2

sensor

Field Connections -- Field connections for accessory

sensors and input devices are made the RTU--MP, at plugs

J1, J2, J4, J5, J11 and J20. All field control wiring that

connects to the RTU--MP must be routed through the

raceway built into the corner post as shown in Fig. 23.

The raceway provides the UL required clearance between

high-- and low--voltage wiring. Pass the control wires

through the hole provided in the corner post, then feed the

wires thorough the raceway to the RTU--MP. Connect to

the wires to the removable Phoenix connectors and then

reconnect the connectors to the board.

Space Temperature (SPT) Sensors

A field--supplied Byrant space temperature sensor is

required with the RTU--MP to monitor space temperature.

There are 3 sensors available for this application:

S

33ZCT55SPT, space temperature sensor with override
button

S

33ZCT56SPT, space temperature sensor with override
button and setpoint adjustment

S

33ZCT59SPT, space temperature sensor with LCD
(liquid crystal display) screen, override button, and
setpoint adjustment

Use 20 gauge wire to connect the sensor to the controller.

The wire is suitable for distances of up to 500 ft. Use a

three--conductor shielded cable for the sensor and setpoint

adjustment connections. If the setpoint adjustment

(slidebar) is not required, then an unshielded, 18 or 20

gauge, two--conductor, twisted pair cable may be used.

Connect T--55 -- See Fig. 40 for typical T--55 internal

connections. Connect the T--55 SEN terminals to

RTU--MP J20--1 and J20--2. See Fig. 41.

2

3

4

5

6

1

SW1

SEN

BRN (GND)

BLU (SPT)

RED(+)

WHT(GND)

BLK(-)

CCN COM

SENSOR WIRING

C08201

Fig. 40 -- T--55 Space Temperature Sensor Wiring

SEN

SEN

J20-1

J20-2

C08460

Fig. 41 -- RTU--MP T--55 Sensor Connections

Connect T--56 -- See Fig. 42 for T--56 internal

connections. Install a jumper between SEN and SET

terminals as illustrated. Connect T--56 terminals to

RTU--MP J20--1, J20--2 and J20--3 per Fig. 43.

2

3

4

5

6

1

SW1

SEN

SET

Cool

Warm

BRN (GND)

BLU (SPT)

RED(+)

WHT(GND)

BLK(-)

CCN COM

SENSOR WIRING

JUMPER
TERMINALS
AS SHOWN

BLK
(T56)

C08202

Fig. 42 -- T--56 Internal Connections