X

C

G

W2

C

W2

G

W1

O/B/Y2

Y2

R

W1

R

Y1

Y1

T
H
E
R
M
O
S
T
A
T

(Note 1)

(Note 2)

Note 1: Typical multi-function marking. Follow manufacturer’s configuration

Instructions to select Y2.

Note 2: Y2 to Y2 connection required on single-stage cooling units when

integrated economizer function is desired.

Field Wiring

Central

Terminal

Board

Typical

Thermostat

Connections

C08069

Fig. 22 -- Low--Voltage Connections

Unit without thru--base connection kit —

Pass the thermostat control wires through the hole

provided in the corner post; then feed the wires through

the raceway built into the corner post to the control box.

Pull the wires over to the terminal strip on the upper--left

corner of the Controls Connection Board. See Fig. 23.

RACEWAY

HOLE IN END PANEL (HIDDEN)

C08027

Fig. 23 -- Field Control Wiring Raceway

NOTE:

If thru--the--bottom connections accessory is

used, refer to the accessory installation instructions for
information on routing power and control wiring.
Heat Anticipator Settings —

Set heat anticipator settings at 0.14 amp for the first stage

and 0.14 amp for second--stage heating, when available.

Electric Heaters

551J units may be equipped with field--installed accessory

electric heaters. The heaters are modular in design, with

heater frames holding open coil resistance wires strung

through ceramic insulators, line--break limit switches and

a control contactor. One or two heater modules may be

used in a unit.
Heater modules are installed in the compartment below

the indoor (supply) fan outlet. Access is through the

indoor access panel. Heater modules slide into the

compartment on tracks along the bottom of the heater

opening. See Fig. 24, Fig. 25 and Fig. 26.

DISCONNECT MOUNTING
LOCATION

UNIT BLOCK-OFF
PANEL

OUTDOOR
ACCESS PANEL

INDOOR
ACCESS
PANEL

C08133

Fig. 24 -- Typical Access Panel Location (3--6 Ton)

Not all available heater modules may be used in every

unit. Use only those heater modules that are UL listed for

use in a specific size unit. Refer to the label on the unit

cabinet for the list of approved heaters.
Unit heaters are marked with Heater Model Numbers. But

heaters are ordered as and shipped in cartons marked with

a corresponding heater Sales Package part number. See

Table 2 for correlation between heater Model Number and

Sales Package part number.
NOTE: The value in position 9 of the part number differs
between the sales package part number (value is 1) and a
bare heater model number (value is 0).

Table 2 – Heater Model Number

Bare Heater Model Number

C

R

H

E

A

T

E

R

0

0

1

A

0

0

Heater Sales Package PNO

Includes:

Bare Heater

Carton and packing materials

Installation sheet

C

R

H

E

A

T

E

R

1

0

1

A

0

0