Warning, Step 9 — install external condensate trap and line, Step 10 — make electrical connections – Bryant 551J User Manual

Page 11

Advertising
background image

11

Step 9 — Install External Condensate Trap

and Line

The unit has one

3

/

4

-in. condensate drain connection on

the end of the condensate pan and an alternate connection

on the bottom. See Fig. 13. Unit airflow configuration

does not determine which drain connection to use. Either

drain connection can be used with vertical or horizontal

applications.

DRAIN

(FACTORY-INSTALLED)

PLUG

CONDENSATE PAN (SIDE VIEW)

STANDARD

SIDE DRAIN

ALTERNATE

BOTTOM DRAIN

C08021

Fig. 13 -- Condensate Drain Pan (Side View)

When using the standard side drain connection, ensure the

red plug in the alternate bottom connection is tight. Do this

before setting the unit in place. The red drain pan plug can

be tightened with a

1

/

2

--in. square socket drive extension.

To use the alternate bottom drain connection, remove the

red drain plug from the bottom connection (use a

1

/

2

--in.

square socket drive extension) and install it in the side

drain connection.

The piping for the condensate drain and external trap can

be completed after the unit is in place. See Fig. 14.

NOTE: Trap should be deep enough to offset maximum unit static

difference. A 4” (102) trap is recommended

.

MINIMUM PITCH

1” (25mm) PER

10’ (3m) OF LINE

BASE RAIL

OPEN

VENT

TO ROOF

DRAIN

DRAIN PLUG

ROOF

CURB

SEE NOTE

2˝ (51) MIN

C08022

Fig. 14 -- Condensate Drain Piping Details

All units must have an external trap for condensate

drainage. Install a trap at least 4-in. (102 mm) deep and

protect against freeze-up. If drain line is installed

downstream from the external trap, pitch the line away
from the unit at 1-in. per 10 ft (25 mm in 3 m) of run. Do

not use a pipe size smaller than the unit connection

(

3

/

4

-in.).

Step 10 — Make Electrical Connections

ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal

injury or death.
Do not use gas piping as an electrical ground. Unit

cabinet must have an uninterrupted, unbroken

electrical ground to minimize the possibility of

personal injury if an electrical fault should occur. This

ground may consist of electrical wire connected to

unit ground lug in control compartment, or conduit

approved for electrical ground when installed in

accordance with NEC (National Electrical Code);

ANSI/NFPA 70, latest edition (in Canada, Canadian

Electrical

Code

CSA

[Canadian

Standards

Association] C22.1), and local electrical codes.

!

WARNING

NOTE: Check all factory and field electrical connections
for tightness. Field--supplied wiring shall conform with
the limitations of 63_F (33_C) rise.
Field Power Supply —

If equipped with optional Powered Convenience Outlet:

The power source leads to the convenience outlet’s

transformer primary are not factory connected. Installer

must connect these leads according to required operation

of the convenience outlet. If an always--energized

convenience outlet operation is desired, connect the

source leads to the line side of the unit--mounted

disconnect. (Check with local codes to ensure this method

is acceptable in your area.) If a de--energize via unit

disconnect switch operation of the convenience outlet is

desired, connect the source leads to the load side of the

unit disconnect. On a unit without a unit--mounted

disconnect, connect the source leads to compressor

contactor C and indoor fan contactor IFC pressure lugs

with unit field power leads.

Refer to Fig. 19 for power transformer connections and

the discussion on connecting the convenience outlet on

page 12.

Field power wires are connected to the unit at line--side

pressure lugs on compressor contactor C and indoor fan

contactor IFC (see wiring diagram label for control box

component arrangement) or at factory--installed option

non--fused disconnect switch. Max wire size is #2 AWG

(copper only). (See Fig. 15.)
NOTE: TEST LEADS -- Unit may be equipped with
short leads (pigtails) on the field line connection points on
contactor C or optional disconnect switch. These leads are
for factory run--test purposes only; remove and discard
before connecting field power wires to unit connection

points. Make field power connections directly to line
connection pressure lugs only.

551J

j

Advertising