Bryant 551J User Manual

Page 16

Advertising
background image

16

DISCONNECT
MOUNTING
LOCATION

EMT OR RIGID CONDUIT
(FIELD-SUPPLIED)

SINGLE
POINT BOX

CENTER
POST

HEATER
COVERS

HEATER
MOUNTING
BRACKET

HEATER
MODULE
(LOCATION 2)

HEATER
MODULE
(LOCATION 1)

SINGLE POINT
BOX
MOUNTING
SCREW

BRACKET AND
CONDUIT
DRIP BOOT

MAIN
CONTROL
BOX

CONTROL WIRE TERMINAL BLOCK

MANUAL RESET
LIMIT SWITCH

C08134

Fig. 25 -- Typical Component Location

TRACK

FLANGE

C08135

Fig. 26 -- Typical Module Installation

Single Point Boxes and Supplementary Fuses — When

the unit MOCP device value exceeds 60--A, unit--mounted

supplementary fuses are required for each heater circuit.

These fuses are included in accessory Single Point Boxes,

with power distribution and fuse blocks. The single point

box will be installed directly under the unit control box,

just to the left of the partition separating the indoor

section (with electric heaters) from the outdoor section.

The Single Point Box has a hinged access cover. See

Fig. 27. The Single Point Box also includes a set of

power taps and pigtails to complete the wiring between

the Single Point Box and the unit’s main control box

terminals. Refer to the accessory heater and Single Point

Box installation instructions for details on tap

connections.
All fuses on 551J units are 60--A. (Note that all heaters are

qualified for use with a 60--A fuse, regardless of actual

heater ampacity, so only 60--A fuses are necessary.)
Single Point Boxes without Fuses — Unit heater

applications not requiring supplemental fuses require a

special Single Point Box without any fuses. The accessory

Single Point Boxes contain a set of power taps and pigtails

to complete the wiring between the Single Point Box and

the unit’s main control box terminals. Refer to accessory

heater and Single Point Box installation instructions for

details on tap connections.

ALLIED PA

MODEL NO.

ERIAL NO.

CORP.

11

13

21

23

OD

22.2

3

1

23

ISTED AIR

NDITIONING

UIP ACCESS
346N.

P / N

2-

5610-4

REV

1

1

13

2

1

2

3

CONTROL
BOX

BUSHING

SINGLE
POINT BOX
MOUNTING
SCREWS

FOAM
BUSHING

DRIP BOOT
BRACKET
MOUNTING
SCREWS

HEATER
RELAYS

POWER
WIRES

HEATER
MOUNTING
SCREWS

C08136

Fig. 27 -- Typical Single Point Installation

Low--Voltage Control Connections — Pull the

low--voltage control leads from the heater module(s) --

VIO and BRN (two of each if two modules are installed;

identify for Module #1) -- to the 4--pole terminal board

TB4 located on the heater bulkhead to the left of Heater

#1. Connect the VIO lead from Heater #1 to terminal

TB4--1. For 2 stage heating, connect the VIO lead from

Heater #2 to terminal TB4--2. For 1 stage heating with 2

heater modules connect the VIO lead from both Heater #1

and #2 to terminal TB4--1. Connect both BRN leads to

terminal TB4--3. See Fig. 28.

ORN

BRN

Field
Connections

HR1: On Heater 1 in Position #1
HR2: On Heater 2 in Position #2 (if installed)

2

3

12

1

3

VIO

ORN

VIO

BRN

VIO

BRN BRN

VIO

2

TB4

VIO

HR2

HR1

BRN

VIO

BRN

Elec Htr

CTB

CONTL
BOARD

C08331

Fig. 28 -- Accessory Electric Heater Control

Connections

551J