RTU--MP control system —

The RTU--MP controller, see Fig. 36, provides expanded

stand--alone operation of the HVAC system plus

connection and control through communication with

several Building Automation Systems (BAS) through

popular third--party network systems. The available

network systems are BACnet MP/TP, Modbus and

Johnson J2. Communication with LonWorks is also

possible by adding an accessory interface card to the

RTU--MP. Selection of the communication protocol and

baud rate are made at on--board DIP switches.

The RTU--MP control is factory--mounted in the 551J

unit’s main control box, to the left of the CTB. See

Fig. 37. Factory wiring is completed through harnesses

connected to the CTB. Field connections for RTU--MP

sensors will be made at the Phoenix connectors on the

RTU--MP board. The factory--installed RTU--MP control

includes the supply--air temperature (SAT) sensor. The

outdoor air temperature (OAT) sensor is included in the

FIOP/accessory EconoMi$er2 package.

Refer to Table 2, RTU--MP Controller Inputs and Outputs

for locations of all connections to the RTU--MP board.

C07129

Fig. 36 -- RTU--MP Multi--Protocol Control Board

C10049

Fig. 37 -- 551J Control Box Component Locations

551J