Audible alarm, Enabling building management system connection, Building management system stop bits – Bacharach AGM300 User Manual

Page 43: Building management system baud rate, Password

Advertising
background image

Instruction 3015-4275

35

Audible Alarm

This parameter selects the function of the ADM800’s internal audible alarm.

1. Press the AUDIBLE ALARM key to adjust the setting.
2. Use the UP/DOWN cursor keys to select unused, monitor on, evacuate, spill, leak, fault, or alarm.
3. Press ENTER to accept the new entry or QUIT to revert to the previous setting.

Enabling Building Management System Connection

This enables or disables the connection to a Building Management System.

1. Press the BMS key to adjust the setting.
2. Use the UP/DOWN cursor keys to toggle the setting.
3. Press ENTER to accept the new entry or QUIT to revert to the previous setting.

Building Management System Stop Bits

This value is the number of stop bits for the ADM800 on a Building Management System.

1. Press the BMS STOPBITS key to adjust the setting.
2. Use the UP/DOWN cursor keys to modify the setting.
3. Press ENTER to accept the new entry or QUIT to revert to the previous setting.

Building Management System Baud Rate

This is the baud rate of the Building Management System.

1. Press the BMS BAUD key to adjust the setting.
2. Use the UP/DOWN cursor keys to modify the setting.
3. Press ENTER to accept the new entry or QUIT to revert to the previous setting.

Password

This field is used to define a system password. The default setting is 000, which provides no password
protection.

1. Press the PASSWORD key to enter a password.
2. Use the LEFT/RIGHT cursor keys to move across the entry field and the UP/DOWN cursor keys to

modify the individual characters.

3. Press ENTER to accept the new password or QUIT to revert to the previous setting.