Adm800 - specifications, Adm800, Pecifications – Bacharach AGM300 User Manual

Page 92

Advertising
background image

84

Instruction 3015-4275

ADM800 - Specifications

Product Description: The ADM800 Ammonia Display Module provides remote programming, interrogation

and display functionality to support the AGM300 Ammonia Gas Monitor. The system
design supports compliance to the refrigerant monitoring requirements of ANS/BSR
ASHRE 15-1994.

Inputs:

The ADM800 accepts inputs from up to four AGM300 monitors. It offers a wide variety
of displays and can fully program any associated monitor.

Display:

Back lit LCD

Power Indication:

Green LED glows when AC power is applied

Alarm Indication:

Red LED glows and alarm condition is displayed

Fault Indication:

Yellow LED glows and fault condition is displayed

Password Protection: The ADM800 can be password protected to prevent the unauthorized editing of setup

parameters without disturbing the ability to monitor system outputs

Power Safety Mode: Fully automatic system reset; all parameters maintained

Monitoring Distance: Up to 4500 feet from furthest AGM300

Communications:

Full two-way communication with AGM300 monitors via RS-485 interface. A second
RS-485 interface provided for connection to a Building Management System.

Relays:

Two SDDT programmable alarm contacts are provided (Rated 5 amp 120 VAC)

Operating Temp:

32 to 113 °F (0 to 45 °C)

Ambient Humidity:

5 to 90% (non-condensing)

Size/Weight:

11"H x 10"W x 3"D - 5 lbs.

AC Power:

120 to 230 VAC, 50/60 Hz, 21 Watts

Mounting: Wall

mount

Certification:

UL 61010-1 and CE Mark

Warranty:

Two (2) Years from date of shipment

Altitude Limit: 2,000

Meters