Zone Hold Mode

A zone can be placed on hold and continuously monitored for a length of time determined by the Zone Hold
Time value (Page 38). To place a zone on hold, press and hold down the key adjacent to that zone until you
hear a beep. The word "HOLDING" appears to identify which zone is being held.

Zone Screen (Hold Mode)

Once in the hold mode you can further investigate the status of the zone by pressing the adjacent key and going
to the Zone Setup #1 Screen (Page 41). To release the zone from the hold mode, press and hold down the
adjacent key until the unit beeps and the screen display reverts to normal. You may also press and hold down
the key adjacent to any other zone to release the current zone and put the new zone on hold.

Alarm Conditions

When an alarm condition is detected anywhere on the network the red ALARM LED will glow. Additionally, an
external alarm device may activate and an audible alarm may sound if those features have been enabled
(Pages 28 & 35).

An inverse flashing box indicates an alarm condition in the affected zone.

Zone Screen (Alarm Mode)