Bryant ASPAS1BBA015 User Manual

Page 105

Advertising
background image

SECTION 4.4

DIAGNOSTIC TESTS

DC CONTROL

TEST 52 - TEST FUEL SOLENOID

Note: This test is for fuel regulators equipped with
idle circuit port only. See Figure 16. These units
have an additional 1/4” fuel hose.

DISCUSSION:
When the Fuel Solenoid (FS) is energized, gas
pressure is available internally to the on demand Fuel
Regulator. Gas pressure will then be available to the
idle circuit port of the Fuel Regulator.

PROCEDURE:

1. Disconnect Wire 56 from the starter contactor relay

(SCR). This will disable the unit from cranking. For
single cylinder units, disconnect from the starter
contactor (SC) and isolate it from ground.

2. Remove the fuel hose from the idle circuit port barbed

fitting.

3. Attach a manometer (Generac P/N 0C7977) to the idle

circuit port barbed fitting.

4. Set the Auto-Off-Manual switch to MANUAL. The engine

will not crank, but gas pressure should be observed on
the manometer at 11”-14” of water column.

5. Set the Auto-Off-Manual switch to OFF. Remove the

manometer. Re-attach the fuel hose to the idle circuit
port barbed fitting. Re-connect Wire 56 to the starter
contactor relay or starter contactor.

RESULTS:

1. If gas pressure was measured, proceed to Test 55.

2. If gas pressure was not measured, replace the fuel

solenoid (FS).

TEST 53 - CHECK CIRCUIT BOARD WIRE 14

OUTPUT

DISCUSSION:
During any cranking action, the circuit board's crank
relay (K1) and run relay (K2) both energize
simultaneously. When the run relay energizes, its
contacts close and 12 volts DC is delivered to Wire 14
and to a fuel solenoid. The solenoid energizes open
to allow fuel flow to the engine. This test will
determine if the circuit board is working properly.

PROCEDURE:

1. Set the Auto-Off-Manual switch to OFF.

2. Connect the positive (+) test lead of a DC voltmeter (or

VOM) into Pin 7 (Wire 14) of the circuit board connector
J1. Connect the common (-) test lead to frame ground.

3. While observing the meter, set the Auto-Off-Manual

switch to MANUAL.

a. The circuit board's crank and run relays should

energize and the engine should crank and start.

b. The meter should indicate battery voltage.

c. If battery voltage is indicated, proceed to Step 4.

If battery voltage is NOT indicated, proceed to
Test 53 results.

4. Disconnect Wire 14 at the Fuel Solenoid (FS).

a. Connect the positive (+) test lead to Wire 14.

Connect the negative test lead to a clean frame
ground. Set the Auto-Off-Manual switch to
MANUAL. Battery voltage should be measured.
If battery voltage is indicated, proceed to Step 5.

b. Connect the positive (+) test lead to Wire 14 at

the 4-tab terminal block in the control panel, see
Figure 17. Connect the negative (-) test lead to
frame ground. While observing the meter, set
the Auto-Off-Manual switch to MANUAL. Battery
voltage should be measured.

Figure 17. 4-Tab Terminal Block

5. Set the VOM to it’s “R x 1” scale.

6. Disconnect Wire 0 from the Fuel Solenoid (FS). Connect

one test lead to Wire 0 and the other test lead to a clean
frame ground. CONTINUITY should be measured.

RESULTS:

1. If the engine cranks but does not start and battery

voltage was not measured in Step 3, replace the circuit
board.

2. If the engine cranks and battery voltage was measured

in Step 3, but there was no battery voltage in Step 4(a),
repair or replace Wire 14 between 4-tab terminal block
and the Fuel Solenoid (FS).

3. If the engine cranks and battery voltage was measured

in step 3 and no battery voltage is measured in step 4b,
repair or replace Wire 14 between the J1 connector on
the circuit board and the 4-tab terminal block.

4. If the engine cranks but does not start and battery

voltage was measured in Steps 2, 3 and 4, and
CONTINUITY was not measured in Step 6, repair or
replace Wire 0 between the Control Panel ground

PART 4

Page 105

Advertising