SECTION 4.2

OPERATIONAL ANALYSIS

PART 4

DC CONTROL

UTILITY VOLTAGE DROPOUT / ENGINE

CRANKING

• After fifteen (15) seconds and when the circuit

board's 15-second timer has timed out, if "Utility"
voltage is still below 60 percent of nominal, circuit
board action will energize the circuit board's crank
and run relays (K1 and K2) simultaneously.

• The crank relay (K1) will remain energized for about

15 seconds on the first crank cycle. The relay will
then de-energize for 7 seconds and will again
energize. This time it will remain energized for 7

seconds. Thus, the engine will crank cyclically for 7
second crank-rest cycles. This cyclic cranking will
continue until either the engine starts or until about
ninety (90) seconds of crank-rest cycles have
elapsed.

• When the crank relay (K1) is energized, circuit board

action delivers 12 volts DC to a starter contactor
relay (SCR), via Wire 56. When the SCR energizes,
its contacts close and battery power is delivered to a
starter contactor (SC). When the SC energizes, its
contacts close and battery power is delivered to the
starter motor (SM).The engine cranks.

CHARGER

BATTERY

0

162

22

VOLTAGE

REGULATOR

ELECTRONIC

6

4

0

11

(STATOR)

DPE WINDING

C2-8

2

C2-7

C2-11

C2-10

CB2

4

0

22

6

BA

FIELD

0

13

11

0

77

C2-1

3

1

2

C1-3

14

11

16

17

12

13

15

14

C2-3

PRINTED CIRCUIT

0

C1-6

C2-9

0

0

55

C2-4

4

0

WINDING

ENGINE RUN

(STATOR)

66

CONTROL

BOARD

3

2

1

J2

3

7

9

4

6

5

J1

5

4

1

2

66A

66A

85

351

HTO

C1-4

C2-2

0

0

SW2

17

225

15

224

0

66A

14

194

23

194

56

15A

66A

239

18

86

23

224

4

86

0

LOP

14

225

239

15A

23

194

13

225B

BATTERY CHARGE

WINDING

13

1

2

77

224B

11

22

1

6

66

3

4

225A

224A

9

7

7

9

BCR

0

14

13

13

13

0

0

224

225A

225

224A

22

11

0

0

15A

TX - TRANSFORMER, 16 Vac 56 VA & 16 Vac 1 VA (DUAL SEC.)

DIAGRAM KEY

BA - BRUSH ASSEMBLY

SCR - STARTER CONTACTOR RELAY

SC - STARTER CONTACTOR

HTO - HIGH OIL TEMPERATURE SWITCH

FS - FUEL SOLENOID

CB1 - CIRCUIT BREAKER, MAIN OUTPUT

LOP - LOW OIL PRESSURE SWITCH

IM2 - IGNITION MODULE, CYLINDER #2

IM1 - IGNITION MODULE, CYLINDER #1

SW1 - AUTO / OFF / MANUAL SWITCH

SM - STARTER MOTOR

SW2 - SET EXERCISE SWITCH

SP1, SP2 - SPARK PLUGS

CB2 - CIRCUIT BREAKER, ALT. EXCITATION

BCR - BATTERY CHARGE RELAY

F2 - FUSE 7.5 AMP

D - DIODE

F1 - FUSE 15 AMP

CB3 - CIRCUIT BREAKER, EXTERNAL OUTLET, PUSH/PULL

= 12 VDC ALWAYS PRESENT

= AC VOLTAGE

= GROUND FOR CONTROL PURPOSES

= 12 VDC DURING CRANKING ONLY

= DC FIELD CONTROL VOLTAGE

= 12 VDC DURING ENGINE RUN CONDITION

Advertising