Automatic operating sequences chart – Bryant ASPAS1BBA015 User Manual

Page 23

Advertising
background image

GENERAL INFORMATION

SECTION 1.7

AUTOMATIC OPERATING PARAMETERS

PART 1

Page 23

AUTOMATIC OPERATING SEQUENCES CHART

SEQ. CONDITION

ACTION

SENSOR, TIMER OR OTHER

1

Utility source voltage is

No action

Voltage Dropout Sensor on circuit

available.

circuit board.

2

Utility voltage dropout below

A 15-second timer on circuit

Voltage Dropout Sensor and 15

60% of rated voltage occurs.

board turns on.

second timer on circuit board.

3

Utility voltage is still below

15-second timer runs for 15

Voltage Dropout Sensor and 15

60% of rated voltage.

seconds, then stops.

second timer.

4

Utility voltage is still low after

Circuit board action energizes a

Circuit board crank and run

15 seconds.

crank relay and a run relay.

relays.

See NOTE 1.

5

Utility voltage still low and

Circuit board’s “engine warmup

Engine Warmup Timer (10 seconds)

the engine has started.

timer” runs for 10 seconds.

6

Engine running and “engine

Circuit board action energizes a

Circuit board transfer relay circuit

warmup timer” times out.

transfer relay in transfer switch

Transfer switch transfer relay.

AC output voltage above

and transfer to “Standby” occurs.

50% nominal voltage.

7

Engine running and load is

No further action

Circuit

board voltage pickup

powered by Standby power.

sensor continues to seek an
acceptable “Utility” voltage.

8

Utility source voltage is

Circuit board “voltage pickup

Voltage Pickup Sensor (80%)

restored above 80% of rated

sensor” reacts and a “re-transfer

Return to Utility Timer (15 seconds)

time delay” turns on.

9

Utility voltage still high after 15

“Return to Utility Timer” times out

Return to Utility Timer

seconds.

10

Utility voltage still high.

Circuit board action opens the

Circuit board transfer relay circuit

transfer relay circuit to ground.

Transfer switch transfer relay.

Transfer relay de-energizes and
retransfer to “Utility” occurs.

11

Engine still running, loads are

Circuit board “engine cool down

Circuit board Engine Cool down

powered by Utility source.

timer” starts running.

Timer (1 minute)

12

After 1 minute, “engine cool down Engine Cool down Timer
timer” stops and circuit board’s

Circuit board Run Relay.

run relay de-energizes. Engine
shuts down.

13

Engine is shut down, loads are

No action.

Voltage Dropout Sensor on circuit

powered by “Utility” source.

circuit board.

Return to Sequence 1.