Diagnostic tests part 4 – Bryant ASPAS1BBA015 User Manual

Page 98

Advertising
background image

Page 98

SECTION 4.4

DIAGNOSTIC TESTS

PART 4

DC CONTROL

PROCEDURE:
Disconnect all wires from switch terminals, to prevent
interaction. Then, use a volt-ohm-milliammeter (VOM)
to test for continuity across switch terminals as shown
in the following chart. Reconnect all wires and verify
correct positions when finished.

RESULTS:

1. Replace Auto-Off-Manual switch, if defective.

2. For Problem 8 Only: If the switch passes the tests, verify

the remote not auto dip switch is set to OFF on the
circuit board (see Figure 3, Section 4.1) then proceed to
Test 44.

3. For Problem 9 Only: If the switch passes the tests,

proceed to Test 60.

Figure 2. Auto-Off-Manual Switch Test Points

TEST 44- CHECK WIRE 15/15A/17/239

VOLTAGE

DISCUSSION:
The circuit board will not turn on unless battery
voltage is available to the board via wire 15, the Auto-
Off-Manual switch and Wire 15A. If battery voltage is
not available, automatic or manual operation will not
be possible.
Battery voltage is available to wire 17 from pin
location 11 of the J1 connector on the circuit board.
When the Auto-Off-Manual switch is in the MANUAL
position, wire 239 supplies battery voltage to pin
location 9 of the circuit board, and engine cranking
occurs.

PROCEDURE:
(For Problem 1 flow chart, do Steps 1-5 and Step 9
only)
(For Problem 2 flow chart, do all steps)

1. Set a VOM to measure DC voltage.

2. Connect the positive (+) test lead to the Auto-Off-Manual

switch Terminal 2, Wire 15. Connect the negative (-)
test lead to a clean frame ground. Battery voltage
should be measured (See Figure. 2).

3. Connect the positive (+) test lead to the Auto-Off-Manual

switch terminal 1, Wire 15A. Connect the negative (-)
test lead to a clean frame ground. Set the Auto-Off-
manual switch to MANUAL. Battery voltage should be
measured.

4. Connect the positive (+) test lead to Pin location 12 Wire

15 at the J1 connector on the circuit board. Connect the
negative (-) test lead to a clean frame ground. Battery
voltage should be measured.

5. Connect the positive (+) test lead to pin location 10, wire

15A at the J1 connector on the circuit board. Connect
the negative test lead to a clean frame ground. Set the
Auto-Off-Manual switch to the MANUAL position.
Battery voltage should be measured. Repeat Step 5.
This time set the Auto-Off-Manual switch to AUTO.
Battery voltage should be measured.

6. Connect the positive (+) test lead to pin location 9, wire

239 at the J1 connector on the circuit board. Connect
the negative (-) test lead to a clean frame ground. Set
the Auto-Off-Manual switch to the MANUAL position.
Battery voltage should be measured. If battery voltage
is measured, stop and proceed to results. If battery
voltage is not measured, proceed to Step 7.

7. Connect the positive (+) test lead to the Auto-Off-Manual

2

5

6

4

3

1

1

2

3

4

5

6

SW1

SW1

SCHEMATIC

MANUAL

AUTO

15

15A

239

17

15

15

15A

239

17

TERMINALS

SWITCH POSITION

READING

2 and 3

AUTO

C

ONTINUITY

MANUAL

I

NFINITY

OFF

I

NFINITY

2 and 1

AUTO

I

NFINITY

MANUAL

C

ONTINUITY

OFF

I

NFINITY

5 and 6

AUTO

C

ONTINUITY

MANUAL

I

NFINITY

OFF

I

NFINITY

5 and 4

AUTO

I

NFINITY

MANUAL

C

ONTINUITY

OFF

I

NFINITY

Advertising