SECTION 4.4

DIAGNOSTIC TESTS

J1-4, Wire 194

If CONTINUITY was measured, go
to Step 4. Average nominal
resistance reading: 110-120 ohms.

J1-5, Wire 56

If CONTINUITY was measured, go
to Step 5. Average nominal
resistance reading V-twin (SCR):
150-160 ohms, Single Cylinder (SC):
4 ohms.

J1-10, Wire 15A

If CONTINUITY was measured,
repair or replace shorted to ground
Wire 15A between Connector J1 and
switch SW1.

J1-7, Wire 14

If CONTINUITY was measured, go
to Step 6.

NOTE: (V-twins only) Disconnect Wire 16 from the
Starter Contactor Relay (SCR). Connect one test
lead to ground and the other test lead to Wire 16.
Starter Contactor (SC) resistance should be
measured (?? ohms). If continuity is measured,
repair or replace shorted Starter Contactor or
shorted Wire 16 to ground.

4. Disconnect Wire 194 from the terminal strip. Repeat

Step 3 at Pin Location J1-4.

a. If CONTINUITY was measured, Wire 194 is

shorted to ground between Connector J1 and
terminal strip.

b. If INFINITY was measured, disconnect Wire 194

from the transfer switch terminal strip. Connect
one meter test lead to the end of Wire 194
which was removed from the transfer switch
terminal strip. Connect the other meter test lead
to the ground terminal. If CONTINUITY was
measured, Wire 194 is shorted to ground
between the generator and the transfer switch.

1)

If INFINITY was measured, disconnect Wire
194 from the transfer relay (TR). Connect
one meter test lead to the transfer relay
terminal from which Wire 194 was
previously removed. Connect the other test
lead to Wire 23 at the transfer switch
terminal strip. If CONTINUITY “ZERO
RESISTANCE” was measured, replace the
transfer relay. Normal coil resistance is
approximately 113 ohms.

2)

If coil resistance of 113 ohms was
measured, the short is in Wire 194 between
the transfer relay and the terminal strip.
Repair or replace Wire 194.

5. Disconnect Wire 56 From the starter contactor relay

(SCR on V-twin) or the starter contactor (SC on single
cylinder). Connect one meter test lead to the SCR or SC
terminal from which Wire 56 was removed. Connect the
other meter test lead to the ground terminal. If
CONTINUITY or zero resistance was measured,

replace the SCR or SC. Coil resistance for the SCR is
155 ohms. Coil resistance for the SC is 4 ohms. If coil
resistance was measured, Wire 56 is shorted to ground
between Connector J1 and the SCR or SC. Repair or
replace the shorted wire.

6. Disconnect and isolate each Wire 14 from the 4-tab

insulated terminal block. Repeat Step 3 for Pin Location
J1-7. If CONTINUITY was measured, repair or replace
Wire 14 between Connector J1 and the 4-tab terminal
block. If INFINITY was measured, proceed as follows:

a. Disconnect Wire 14 from the following: fuel

solenoid (FS), battery charge relay (BCR) and
hourmeter (HM) if equipped.

b. Connect the negative (-) meter test lead to the

ground terminal. Connect the positive (+) meter
test lead to each of the listed components at the
terminal from which Wire 14 was removed. If
CONTINUITY or zero resistance was measured,
the component has shorted to ground. Replace
the component. The average nominal resistance
value that should be measured for each
component is:

Battery Charge Relay (BCR) - 112 ohms

Fuel Solenoid (FS) - 31 ohms

Hourmeter (HM) - 2 Mega ohms to infinity

c. If each component tests good, there is no short

to ground. The fault exists in one of the Wire 14
wires. Connect one meter test lead to the
ground terminal. Connect the other meter test
lead to each Wire 14 individually (on the end
removed from the BCR, FS or HM). The Wire 14
which measures CONTINUITY is shorted to
ground. Repair or replace the affected wire
between the component and the 4-tab terminal
block.

TEST 77 - TEST EXERCISE FUNCTION

DISCUSSION:
The following parameters must be met in order for the
weekly exercise to occur:
• Auto-Off-Manual switch (SW1) set to AUTO.
• Circuit board DIP Switch 2 (Remote Not Auto) set to

OFF.

PROCEDURE:

1. Set the Auto-Off-Manual switch (SW1) to MANUAL. The

generator should start. Set SW1 back to AUTO. Verify
that SW1 has been in AUTO for weekly exercise to
function.

2. Verify that DIP Switch 2 (Remote Not Auto) on the circuit

board is set to the OFF position (see Figure 1, Section
1.6).

DC CONTROL

PART 4

Page 119