Page 82

ENGINE STARTUP AND RUNNING

With the fuel solenoid open and ignition occurring, the
engine starts. Engine startup and running may be
briefly described as follows:

• An AC voltage/frequency signal is delivered to the

circuit board from the generator engine run winding,
via Wire 66A. When AC frequency reaches
approximately 30 Hz, the circuit board (a)
terminates cranking, and (b) turns on an "engine
warm-up timer".

CHARGER

BATTERY

0

162

22

VOLTAGE

REGULATOR

ELECTRONIC

6

4

0

11

(STATOR)

DPE WINDING

C2-8

2

C2-7

C2-11

C2-10

CB2

4

0

22

6

BA

FIELD

0

13

11

0

77

C2-1

3

1

2

C1-3

4

11

16

17

12

13

15

14

C2-3

PRINTED CIRCUIT

0

C1-6

C2-9

0

0

55

C2-4

4

0

WINDING

ENGINE RUN

(STATOR)

66

CONTROL

BOARD

3

2

1

J2

3

7

9

4

6

5

J1

5

4

1

2

66A

66A

85

351

HTO

C1-4

C2-2

0

0

SW2

17

225

15

224

0

66A

14

194

23

194

56

15A

66A

239

18

86

23

224

4

86

0

LOP

14

225

239

15A

23

194

13

225B

BATTERY CHARGE

WINDING

13

1

2

77

224B

11

22

1

6

66

3

4

225A

224A

9

9

7

7

7

7

9

9

BCR

0

14

13

13

13

0

0

224

225A

225

224A

22

11

0

0

15A

TX - TRANSFORMER, 16 Vac 56 VA & 16 Vac 1 VA (DUAL SEC.)

DIAGRAM KEY

BA - BRUSH ASSEMBLY

SCR - STARTER CONTACTOR RELAY

SC - STARTER CONTACTOR

HTO - HIGH OIL TEMPERATURE SWITCH

FS - FUEL SOLENOID

CB1 - CIRCUIT BREAKER, MAIN OUTPUT

LOP - LOW OIL PRESSURE SWITCH

IM2 - IGNITION MODULE, CYLINDER #2

IM1 - IGNITION MODULE, CYLINDER #1

SW1 - AUTO / OFF / MANUAL SWITCH

SM - STARTER MOTOR

SW2 - SET EXERCISE SWITCH

SP1, SP2 - SPARK PLUGS

CB2 - CIRCUIT BREAKER, ALT. EXCITATION

BCR - BATTERY CHARGE RELAY

F2 - FUSE 7.5 AMP

D - DIODE

F1 - FUSE 15 AMP

CB3 - CIRCUIT BREAKER, EXTERNAL OUTLET, PUSH/PULL

= 12 VDC ALWAYS PRESENT

= AC VOLTAGE

= GROUND FOR CONTROL PURPOSES

= 12 VDC DURING CRANKING ONLY

= DC FIELD CONTROL VOLTAGE

= 12 VDC DURING ENGINE RUN CONDITION

SECTION 4.2

OPERATIONAL ANALYSIS

PART 4

DC CONTROL

Advertising