Bryant ASPAS1BBA015 User Manual

Page 113

Advertising
background image

SECTION 4.4

DIAGNOSTIC TESTS

DC CONTROL

PART 4

Page 113

5. When the highest frequency is reached, maximum

power has been set. From this point turn the adjustment
screw(s) 1/4 turn counterclockwise. The regulator is now
set.

Figure 30

Figure 31

6. Turn utility power to the main distribution panel back on.

This can be done by switching the service main breaker
to the “ON” or closed position. Allow the generator to
shut down.

DO NOT MAKE ANY UNNECESSARY
ADJUSTMENTS. FACTORY SETTINGS ARE
CORRECT FOR MOST APPLICATIONS. HOWEVER,
WHEN MAKING ADJUSTMENTS, BE CAREFUL TO
AVOID OVERSPEEDING THE ENGINE.

TEST 64 - CHECK BATTERY CHARGE

OUTPUT

DISCUSSION:
The battery charging system is a two amp trickle
charge. It is capable of maintaining a charge on a
functional battery. It is not intended to, nor capable of
charging a completely dead battery.
The system will charge when utility source power is
available to the generator or if the generator is
running. The system consists of a transformer (TX),
battery charge relay (BCR), battery charger (BC), and
a battery charge winding. The BCR contacts allow AC
voltage to the battery charger. When the BCR is de-
energized, voltage from the TX is available to the
battery charger. When the generator starts, Wire 14
energizes the BCR. This allows battery charge
winding AC output to power the battery charger.

PROCEDURE:

1. Check the 5 amp fuse (F2).

2. Set the Auto-Off-Manual switch to OFF.

Note: Utility source voltage MUST be available to
the generator.

3. Set a VOM to measure DC amps.

4. Disconnect Wire 13A (purple) from the 5 amp fuse (F2).

5. Connect the positive (+) test lead to Wire 13A, and

connect the negative (-) test lead to the fuse (F2)
terminal from which Wire 13A was removed. The VOM
should measure 50 milliamps to 2.5 amps, depending
upon the state of the charge of the battery.

6. Repeat Step 5. This time set the Auto-Off-Manual switch

to MANUAL. Allow the generator to start and then
measure the current again as in Step 5.

RESULTS:
Follow the Flow Chart in Section 4.3.