Danger – Bryant ASPAS1BBA015 User Manual

Page 123

Advertising
background image

Page 123

SECTION 5.1

SYSTEM FUNCTIONAL TESTS

using the means provided (such as a utility main line
circuit breaker).

THE TRANSFER SWITCH IS NOW
ELECTRICALLY “HOT.” CONTACT WITH “HOT”
PARTS WILL RESULT IN EXTREMELY
HAZARDOUS AND POSSIBLY FATAL
ELECTRICAL SHOCK. PROCEED WITH
CAUTION.

5. Use an accurate AC voltmeter to check utility power

source voltage across transfer switch terminals N1 and
N2. Nominal line-to-line voltage should be 240 volts AC.

6. Check utility power source voltage across terminals N1

and the transfer switch neutral lug; then across terminal
N2 and neutral. Nominal line-to-neutral voltage should
be 120 volts AC.

7. When certain that utility supply voltage is compatible

with transfer switch and load circuit ratings, turn OFF
the utility power supply to the transfer switch.

8. On the generator panel, set the Auto-Off-Manual switch

to MANUAL. The engine should crank and start.

9. Let the engine warm up for about five minutes to allow

internal temperatures to stabilize. Then, set the
generator main circuit breaker to its “ON” (or closed)
position.

PROCEED WITH CAUTION! GENERATOR
POWER VOLTAGE IS NOW SUPPLIED TO THE
TRANSFER SWITCH. CONTACT WITH LIVE
TRANSFER SWITCH PARTS WILL RESULT IN
DANGEROUS AND POSSIBLY FATAL
ELECTRICAL SHOCK.

10.Connect an accurate AC voltmeter and a frequency

meter across transfer switch terminal lugs E1 and E2.
Voltage should be 242-252 volts; frequency should read
about 61-63 Hertz.

11.Connect the AC voltmeter test leads across terminal lug

E1 and neutral; then across E2 and neutral. In both
cases, voltage reading should be 121-126 volts AC.

12.Set the generator main circuit breaker to its OFF (or

open) position. Let the engine run at no-load for a few
minutes to stabilize internal engine generator
temperatures.

13.Set the generator Auto-Off-Manual switch to OFF. The

engine should shut down.

NOTE: It is important that you do not proceed
until you are certain that generator AC voltage
and frequency are correct and within the stated
limits. Generally, if both AC frequency and
voltage are high or low, the engine governor
requires adjustment. If frequency is correct, but
voltage is high or low, the generator voltage
regulator requires adjustment.

GENERATOR TESTS UNDER LOAD

To test the generator set with electrical loads applied,
proceed as follows:

1. Set generator main circuit breaker to its OFF (or open)

position.

2. Turn OFF all loads connected to the Transfer Switch

Terminals T1 and T2.

3. Set the generator Auto-Off-Manual switch to OFF.

4. Turn off the utility power supply to the transfer switch,

using the means provided (such as a utility main line
circuit breaker).

DO NOT ATTEMPT MANUAL TRANSFER
SWITCH OPERATION UNTIL ALL POWER
VOLTAGE SUPPLIES TO THE TRANSFER
SWITCH HAVE BEEN POSITIVELY TURNED
OFF. FAILURE TO TURN OFF ALL POWER
VOLTAGE SUPPLIES WILL RESULT IN
EXTREMELY HAZARDOUS AND POSSIBLY
FATAL ELECTRICAL SHOCK.

5. Manually set the transfer switch to the STANDBY

position, i.e., load terminals connected to the generator
E1/E2 terminals. The transfer switch operating lever
should be down.

6. Set the generator Auto-Off-Manual switch to MANUAL.

The engine should crank and start immediately.

7. Let the engine stabilize and warm up for a few minutes.

8. Set the generator main circuit breaker to its ON (or

closed) position. Loads are now powered by the standby
generator.

9. Turn ON electrical loads connected to transfer switch T1

and T2. Apply an electrical load equal to the full rated
wattage/amperage capacity of the installed generator.

DANGER

DANGER

OPERATIONAL TESTS

AND ADJUSTMENTS

PART 5

Advertising