ELECTRICAL DATA

569D072-120, 576C120, 569F120 UNITS

LEGEND

*Units are suitable for use on electrical systems where voltage supplied

to the unit terminals is not below or above the listed limits.

NOTES:

1. The MCA and MOCP values are calculated in accordance with the

NEC, Article 440.

2. Motor RLA and LRA values are established in accordance with

Underwriters’ Laboratories (UL), Standard 1995.

3. The 575-v units are UL, Canada-listed only.
4. Convenience outlet is available as either a factory-installed option

or a field-installed accessory and is 115-v, 1 ph, 60 Hz.

UNIT

SIZE

FACTORY-

INSTALLED

OPTION

NOMINAL

VOLTAGE

VOLTAGE

RANGE*

COMPRESSOR

FAN MOTORS

(Qty 2)

POWER

SUPPLY

V-Ph-Hz

MIN

MAX

RLA

LRA

FLA (ea)

LRA (ea)

MCA

MOCP

569D

072

NONE OR DISCONNECT

208/230-3-60

187

254

19.2

146

0.9

1.6

25.8

35

CONVENIENCE OUTLET

30.6

35

NONE OR DISCONNECT

460-3-60

418

506

9.6

73

0.4

0.9

12.8

20

CONVENIENCE OUTLET

15.0

20

NONE OR DISCONNECT

575-3-60

523

632

7.7

58.4

0.4

0.9

10.2

15

CONVENIENCE OUTLET

12.0

15

090

NONE OR DISCONNECT

208/230-3-60

187

254

25.6

190

1.5

3.1

35.0

60

CONVENIENCE OUTLET

39.8

60

NONE OR DISCONNECT

460-3-60

418

506

12.8

95

0.7

1.9

17.4

30

CONVENIENCE OUTLET

19.6

30

NONE OR DISCONNECT

575-3-60

523

632

10.2

76

0.7

1.9

13.8

20

CONVENIENCE OUTLET

15.5

20

120

NONE OR DISCONNECT

208/230-3-60

187

254

37.8

239

1.5

3.1

50.3

60

CONVENIENCE OUTLET

55.1

70

NONE OR DISCONNECT

460-3-60

418

506

17.2

125

0.7

1.9

22.9

30

CONVENIENCE OUTLET

25.1

30

NONE OR DISCONNECT

575-3-60

523

632

13.4

80

0.7

1.9

17.8

25

CONVENIENCE OUTLET

19.5

25

576C

120

NONE OR DISCONNECT

208/230-3-60

187

254

36

198

1.5

3.1

48.0

60

CONVENIENCE OUTLET

52.8

70

NONE OR DISCONNECT

460-3-60

418

506

18

99

0.7

1.9

23.9

35

CONVENIENCE OUTLET

26.1

35

NONE OR DISCONNECT

575-3-60

523

632

14

79

0.7

1.9

18.6

30

CONVENIENCE OUTLET

20.3

30

569F

120

NONE OR DISCONNECT

208/230-3-60

187

254

16

125

1.5

3.1

39.0

50

CONVENIENCE OUTLET

43.8

50

NONE OR DISCONNECT

460-3-60

418

506

8

66.5

0.7

1.9

19.4

25

CONVENIENCE OUTLET

21.6

25

NONE OR DISCONNECT

575-3-60

523

632

6.4

50

0.7

1.9

15.8

20

CONVENIENCE OUTLET

17.5

20

FLA

Full Load Amps

LRA

Locked Rotor Amps

MCA

Minimum Circuit Amps

MOCP — Maximum Overcurrent Protection
NEC

National Electrical Code

RLA

Rated Load Amps

50

TF

Q00

4

-0

12

5

69D

07

2-

12

0,

57

6C

12

0,

5

6

9F

120

Advertising
This manual is related to the following products: