ELECTRICAL DATA

566D150-240

LEGEND

*Units are suitable for use on electrical systems where voltage supplied to the

unit terminals is not below or above the listed limits.

†Fuse or HACR circuit breaker.

NOTES:

1. The MCA and MOCP values are calculated in accordance with the National

Electrical Code (NEC), Article 440.

2. Motor RLA and LRA values are established in accordance with Underwrit-

ers’ Laboratories (UL), Standard 1995.

3. The 575-v units are UL, Canada-listed only.

566E150-240

LEGEND

*Units are suitable for use on electrical systems where voltage supplied to the

unit terminals is not below or above the listed limits.

†Fuse or HACR circuit breaker.

NOTES:

1. The MCA and MOCP values are calculated in accordance with the National

Electrical Code (NEC), Article 440.

2. Motor RLA and LRA values are established in accordance with Underwrit-

ers’ Laboratories (UL), Standard 1995.

3. The 575-v units are UL, Canada-listed only.
4. Convenience outlet is available as either a factory-installed option or a field-

installed accessory and is 115-v, 1ph, 60 Hz.

UNIT

SIZE

NOMINAL

VOLTAGE

(3-Ph, 60 Hz)

VOLTAGE

RANGE*

COMPRESSOR

FAN MOTORS (Qty 2)

POWER SUPPLY

RLA

LRA

FLA (ea)

Fan No.

kW

MCA

MOCP†

ICF

Min

Max

1

2

566D

150

208/230

187

253

49.3

191

4.3

3.7

1.41

69.6

100

199

460

414

528

22.1

80

2.3

1.9

31.7

50

84

575

518

660

17.9

69

1.8

1.8

25.6

40

73

180

208/230

187

253

63.6

266

4.3

3.7

1.41

87.5

125

274

460

414

528

29.3

120

2.3

1.9

40.7

60

124

575

518

660

23.8

96

1.8

1.8

33.0

50

100

240

208/230

187

254

67.9

345

4.3

3.7

1.41

93.4

150

353

460

414

508

34.7

173

2.3

1.9

48.1

80

177

575

518

632

28.8

120

1.8

1.8

40.1

60

124

FLA

Full Load Amps

HACR

Heating, Air Conditioning and

Refrigeration

ICF

Maximum Instantaneous Current Flow

During Start-Up (LRA of compressor
plus total FLA of fan motors)

kW

Total Fan Motor Input (kilowatts)

LRA

Locked Rotor Amps

MCA

Minimum Circuit Amps per NEC,

Section 430-24

MOCP — Maximum Overcurrent Protection (amps)
RLA

Rated Load Amps (compressor)

UNIT

SIZE

FACTORY-

INSTALLED

OPTION

NOMINAL

VOLTAGE

(3 Ph, 60 Hz)

VOLTAGE

RANGE*

COMPRESSOR 1

COMPRESSOR 2

FAN MOTORS

Qty 2)

POWER

SUPPLY

FLA (ea)

Fan No.

kW

Min

Max

RLA

LRA

RLA

LRA

1

2

MCA

MOCP†

ICF

566E

150

NONE OR DISCONNECT
CONVENIENCE OUTLET

208/230

187

253

20.7

156

20.7

156

4.3

3.7

1.41

55.6

70

186

63.5

80

194

NONE OR DISCONNECT
CONVENIENCE OUTLET

460

414

528

10.0

75

10.0

75

2.3

1.9

1.41

27.7

35

90

31.3

40

94

NONE OR DISCONNECT
CONVENIENCE OUTLET

575

518

660

8.2

54

8.2

54

1.8

1.8

1.41

23.1

30

67

25.9

30

70

180

NONE OR DISCONNECT
CONVENIENCE OUTLET

208/230

187

253

32.1

195

32.1

195

4.3

3.7

1.41

81.2

100

236

89.2

100

244

NONE OR DISCONNECT
CONVENIENCE OUTLET

460

414

528

16.4

95

16.4

95

2.3

1.9

1.41

42.1

50

117

45.7

60

120

NONE OR DISCONNECT
CONVENIENCE OUTLET

575

518

660

12.0

80

12.0

80

1.8

1.8

1.41

31.6

40

97

34.5

40

99

240

NONE OR DISCONNECT
CONVENIENCE OUTLET

208/230

187

253

37.8

239

37.8

239

4.3

3.7

1.41

94.1

125

286

102.0

150

294

NONE OR DISCONNECT
CONVENIENCE OUTLET

460

414

528

19.2

125

19.2

125

2.3

1.9

1.41

48.4

60

149

52.0

70

153

NONE OR DISCONNECT
CONVENIENCE OUTLET

575

518

660

13.8

80

13.8

80

1.8

1.8

1.41

35.7

45

98

38.5

50

101

FLA

Full Load Amps

HACR

Heating, Air Conditioning and

Refrigeration

ICF

Maximum Instantaneous Current Flow

During Start-Up (LRA of compressor
plus total FLA of fan motors)

kW

Total Fan Motor Input (kilowatts)

LRA

Locked Rotor Amps

MCA

Minimum Circuit Amps per NEC,

Section 430-24

MOCP — Maximum Overcurrent Protection (amps)
RLA

Rated Load Amps (compressor)