PHYSICAL DATA

566D150-240 UNITS

*Unit is factory-supplied with holding charge only.

†Typical operating charge with 25 ft of interconnecting piping. Operating charge is approximate for maximum system

capacity.

**Indicates capacity step (%) with electric unloader accessory.

††Storage capacity is measured at liquid saturated temperatures of 120 F.

UNIT

566D150

566D180

566D240

NOMINAL CAPACITY (tons)

12

1

/

2

15

20

OPERATING WEIGHTS (lb)

Aluminum-Fin Coil (Standard)

779

789

929

Copper-Fin Coil (Optional)

919

929

1040

REFRIGERANT TYPE*

R-22

Operating Charge, Typical (lb)†

23

23

28

Shipping Charge (lb)

3.1

3.1

3.1

COMPRESSOR

Reciprocating, Semi-Hermetic

Qty...Model

1...06DD328

1...06DD537

1...06E4250

No. Cylinders

6

6

4

Speed (rpm)

1750

1750

1750

Oil Charge (pt)

10

10

15.5

Capacity Steps

Accessory

33**, 66, 100

33**, 66, 100

Standard

66, 100

66, 100

50, 100

Unloader Setting (psig)

Load

70 ± 1

Unload

60 ± 2

Crankcase Heater Watts

125

CONDENSER FANS

Axial Flow, Direct Drive

Qty...Rpm

2...1075

Diameter (in.)

26

Nominal Hp

1

/

2

Nominal Airflow (cfm, total)

11,000

Watts (total)

1460

CONDENSER COIL

Copper Tubes, Aluminum Fins

Rows...Fins/in.

3...15

3...15

3...15

Face Area (sq ft)

29.2

29.2

29.2

Storage Capacity (lb)††

48

48

38

CONTROLS

Pressurestat (psig)

High Pressure

Cutout

395 ± 10

Cut-in

295 ± 20

Low Pressure

Cutout

27 ± 4

Cut-in

67 ± 7

FAN CYCLING CONTROLS

Operating Pressure (psig)

No. 2 Fan, Close

255 ± 10

Open

160 ± 10

PRESSURE RELIEF

Location

Liquid Line

Temperature (F)

200

PIPING CONNECTIONS (in. ODM)

Suction

1

3

/

8

1

3

/

8

1

5

/

8

Liquid

5

/

8

Hot Gas Stub

3

/

8

5

0TF

Q00

4

-012