Hydronic heating capacities, Heating correction factors – Bryant 569F User Manual

Page 71

Advertising
background image

71

PERFORMANCE DATA (cont)

HYDRONIC HEATING CAPACITIES

LEGEND

*Based on 5 psig steam, 60 F entering-air temperature. All steam coils

are non-freeze type.

†Based on 200 F entering water, 20 F water temperature drop, 60 F

entering-air temperature.

NOTES:
1. Maximum operating limits for heating coils: 20 psig at 260 F.

2. Leaving db = ent db (F) +

3. See Heating Correction Factors table.

HEATING CORRECTION FACTORS

NOTE: Multiply capacity given in the Hydronic Heating Capacities table by the correction factor for conditions at which unit is actually
operating. Correct leaving-air temperature using formula in Note 2 of Hydronic Heating Capacities table.

UNIT

524A-B
524A-C

AIRFLOW

(Cfm)

1-ROW

STEAM*

2-ROW

HOT WATER COIL†

Cap.

Ldb

Cap.

Ldb

Water

Flow

(Gpm)

PD

072

1,800
2,400
3,000

146
173
209

134
126
123

156.0
183.0
206.0

140
131
124

15.6
18.3
20.6

3.4
4.3
5.2

090

2,250
3,000
3,750

168
209
240

129
123
117

174.0
206.0
238.0

133
124
118

17.4
20.6
23.8

4.0
5.2
6.5

120

3,000
4,000
5,000

209
243
279

123
115
111

299.0
275.0
316.0

152
124
119

29.9
27.5
31.6

5.0
6.6
8.2

150

3,750
5,000
6,250

370
425
465

150
137
128

362.0
409.0
456.0

149
136
128

36.2
40.9
45.6

4.2
5.1
6.0

180

4,500
6,000
7,500

402
458
479

141
129
118

412.0
471.0
529.0

145
133
125

41.2
47.1
52.9

4.5
5.5
6.6

240

6,000
8,000

10,000

458
487
499

129
115
105

506.0
584.0
652.0

138
128
120

50.6
58.4
65.2

5.1
6.3
7.5

300

7,500

10,000
12,500

511
575
626

122
112
106

649.0
752.0
842.0

140
130
122

64.9
75.2
84.2

5.7
7.1
8.5

Cap. —

Capacity (Btuh in thousands)

Lab —

Leaving-Air Dry-Bulb Temp (F)

PD

Pressure Drop (ft water)

Capacity (Btuh)

1.1 x cfm

HOT WATER COIL

Water Temp

Drop

(F)

Ent Water

Temp

(F)

Entering-Air Temp (F)

40

50

60

70

80

10

140

0.72

0.64

0.57

0.49

0.41

160

0.89

0.81

0.74

0.66

0.58

240

1.06

0.98

0.90

0.83

0.75

200

1.22

1.15

1.07

1.00

0.92

220

1.39

1.32

1.24

1.17

1.09

20

140

0.64

0.57

0.49

0.41

0.33

160

0.81

0.74

0.66

0.58

0.51

240

0.98

0.91

0.83

0.75

0.68

200

1.15

1.08

1.00

0.93

0.85

220

1.32

1.25

1.17

1.10

1.02

30

140

0.56

0.49

0.41

0.33

0.24

160

0.74

0.66

0.58

0.51

0.43

240

0.91

0.83

0.76

0.68

0.60

200

1.08

1.00

0.93

0.85

0.78

220

1.25

1.18

1.10

1.03

0.95

STEAM COIL

Steam Pressure

(psig)

Entering-Air Temp (F)

40

50

60

70

80

0

1.06

0.98

0.91

0.85

0.78

2

1.09

1.02

0.95

0.89

0.82

5

1.13

1.06

1.00

0.93

0.87

50
TF
Q00

4

-012

52
4A0

7

2-
30
0