Application data - 566d150-240, 566e150-240, Application data -56 – Bryant 569F User Manual

Page 54

Advertising
background image

54

APPLICATION DATA — 566D150-240, 566E150-240

1. INSTALLATION — Select equipment to match or to be

slightly less than peak load. This provides better humidity
control, less unit cycling, and less part-load operation.

When selecting vapor line sizes, oil return must be evalu-
ated, particularly at part-load conditions.

The indoor fan must always be operating when outdoor unit
is operating.

Ductwork should be sized according to unit size, not build-
ing load.

To minimize the possibility of air recirculation, avoid the use
of concentric supply/return grilles.

Indoor equipment should be selected at no less than
300 cfm/ton.

OPERATING LIMITS

MINIMUM OUTDOOR-AIR OPERATING

TEMPERATURE — 566D150-240 UNITS

*Requires field-installed unloader.

MINIMUM OUTDOOR-AIR OPERATING

TEMPERATURE — 566E150-240 UNITS

LIQUID LINE DATA — 566D150-240 UNITS

NOTE: Data above is for units operating at 45 F saturated suction and
95 F entering air.

LIQUID LINE DATA — 566E150-240 UNITS

2. REFRIGERANT PIPING — It is recommended that the

refrigerant piping for all commercial split systems include a
liquid line solenoid valve, a liquid line filter drier, and a sight
glass.

For refrigerant lines longer than 75 lineal ft, a liquid line
solenoid valve and a suction accumulator are required.
Refer to the Refrigerant Specialties table.

REFRIGERANT SPECIALTIES PART NUMBERS

*Bushings required.

Maximum Outdoor

115 F

Minimum Outdoor Ambient

See Minimum Outdoor-Air
Operating Temperature
table below.

Minimum Return-Air

Temperature

55 F

Maximum Return-Air

Temperature

95 F

Normal Acceptable Saturation

Suction Temperature Range

25 to 55 F

Maximum Discharge

Temperature

295 F

Minimum Discharge Superheat

60 F

UNIT
566D

NO. OF

CYLINDERS

FULL LOAD

CAPACITY

(%)

MINIMUM

OUTDOOR-AIR

OPERATING

TEMPERATURE (F)

Base

Unit

With

Low-Ambient

Control

150

6

100

20

–20

4

67

31

2*

33*

40

180

6

100

20

4

67

33

2*

33*

47

240

4

100

15

2

50

20

UNIT
566E

FULL LOAD

CAPACITY

(%)

SATURATED COND

TEMPERATURE (F)

MINIMUM

OUTDOOR-AIR

TEMPERATURE (F)

Base

Unit

With

Low-Ambient

Control

150

100/50

90

50

–20

180

240

UNIT
566D

MAX

ALLOW.

LIFT

(ft)

LIQUID LINE

Max Allow.

Pressure

Drop

(psi)

Max Allow.

Temp

Loss

(

°F)

150

67

7

2

180

82

240

87

UNIT
566E

MAX

ALLOW.

LIFT

(ft)

LIQUID LINE

Max Allow.

Pressure

Drop

(psi)

Max Allow.

Temp

Loss

(

°F)

150

60

7

2

180
240

UNIT

LIQUID LINE

SIZE (in.)

LIQUID LINE

SOLENOID VALVE (LLSV)

LLSV

COIL

SIGHT

GLASS

FILTER

DRIER

SUCTION LINE

ACCUMULATOR

566D150

1

/

2

200RB7T4M

AMG/24V

AMI-1TT4

P502-8757S*

S-7063

5

/

8

200RA8T5M

AMG/24V

AMI-1TT5

P502-8757S*

S-7063

566D180

1

/

2

200RB7T4M

AMG/24V

AMI-1TT4

P502-8757S*

S-7721

5

/

8

200RA8T5M

AMG/24V

AMI-1TT5

P502-8757S*

S-7721

7

/

8

200RA8T7M

AMG/24V

AMI-1TT7

P502-8757S

S-7721

566D240

5

/

8

200RA9T5M

AMG/24V

AMI-1TT5

P502-8757S*

S-7721

7

/

8

200RA9T7M

AMG/24V

AMI-1TT7

P502-8757S

S-7721

566E150

1

/

2

200RB5T4M Qty 2

AMG/24V Qty 2

AMI-1TT4 Qty 2

P502-8304S Qty 2

S-7063S* Qty 2

566E180

1

/

2

200RB5T4M Qty 2

AMG/24V Qty 2

AMI-1TT4 Qty 2

P502-8304S Qty 2

S-7063S Qty 2

5

/

8

200RB5T5M Qty 2

AMG/24V Qty 2

AMI-1TT5 Qty 2

P502-8304S Qty 2

S-7063S Qty 2

566E240

1

/

2

200RB6T4M Qty 2

AMG/24V Qty 2

AMI-1TT5 Qty 2

P502-8307S*

S-7063S Qty 2

5

/

8

200RB6T5M Qty 2

AMG/24V Qty 2

AMI-1TT5 Qty 2

P502-8307S*

S-7063S Qty 2

5

0TF

Q00

4

-012

56

6D

/E1

50-

24

0