Bryant 569F User Manual

Page 78

Advertising
background image

78

ELECTRICAL DATA (cont)

ELECTRIC HEATER DATA (cont)

LEGEND

*Values shown are for single-point connection of electric heat acces-

sory and air handler.

NOTES:

1. Electrical resistance heaters are rated at 240 v, 480 v, or 575 v. To

determine heater capacity (kW) at unit nameplate multiply the
240-v, 480-v, or 575-v capacity (kW) by the factor shown in the
table below for the unit voltage.

2. The following equation converts kW of heat energy to Btuh:

kW x 3,412 = Btuh.

3. Heater contactor coils are 24 v and require 8 va holding current.
4. Electric heaters are tested and ETL approved at maximum total

external static pressure of 1.9 in. wg.

5. MCA and MOCP values apply to both standard and alternate fac-

tory-supplied motors.

6. Approximate shipping weight for CAELHEAT001A00-015A00 is

55 lb each, CAELHEAT016A00-027A00 is 60 lb each, and
CAELHEAT028A00-039A00 is 75 lb each.

HEATER PART NO.

UNIT

V-PH-Hz

FAN MOTOR

ELECTRIC HEATER(S)

MCA*

MOCP*

Nominal Capacity (kW)

Actual Capacity (kW)

FLA

Hp

kW

FLA

Stage 1 Stage 2 Total

CAELHEAT034A00

524A-B300
524A-C300

208-3-60

7.5

5.59 19.8

50

22.6

15.0

37.6

104.3

157.2

175

10.0 7.46 28.0

50

22.6

15.0

37.6

104.3

165.6

175

240-3-60

7.5

5.59 19.4

50

30.0

20.0

50.0

120.3

174.6

200

10.0 7.46 26.8

50

30.0

20.0

50.0

120.3

183.9

200

CAELHEAT035A00

480-3-60

7.5

5.59

9.7

50

30.0

20.0

50.0

60.1

87.3

90

10.0 7.46 13.4

50

30.0

20.0

50.0

60.1

91.9

100

CAELHEAT036A00

575-3-60

7.5

5.59

7.8

50

30.0

20.0

50.0

50.2

72.5

80

10.0 7.46 10.3

50

30.0

20.0

50.0

50.2

75.6

80

CAELHEAT037A00

208-3-60

7.5

5.59 19.8

70

30.0

22.6

52.6

145.9

172.8

175

10.0 7.46 28.0

70

30.0

22.6

52.6

145.9

181.2

200

240-3-60

7.5

5.59 19.4

70

40.0

30.0

70.0

168.4

192.6

200

10.0 7.46 26.8

70

40.0

30.0

70.0

168.4

201.9

225

CAELHEAT038A00

480-3-60

7.5

5.59

9.7

70

40.0

30.0

70.0

84.2

96.3

100

10.0 7.46 13.4

70

40.0

30.0

70.0

84.2

100.9

110

CAELHEAT039A00

575-3-60

7.5

5.59

7.8

70

40.0

30.0

70.0

70.3

80.0

90

10.0 7.46 10.3

70

40.0

30.0

70.0

70.3

83.2

90

FLA

Full Load Amps

Hp

Horsepower

MCA

Minimum Circuit Amps

MOCP — Maximum Overcurrent Protection (Amps)

HEATER

RATING

VOLTAGE

ACTUAL HEATER VOLTAGE

200

208

230 240 400

440

460 480 550 575 600

240

0.694 0.751 0.918

1

480

— 0.694 0.84 0.918

1

575

— 0.915

1

1.089

50

TF

Q00

4

-0

12

524

A

0

72-

30

0

Advertising