Bryant 569F User Manual

Page 35

Advertising
background image

35

PHYSICAL DATA (cont)

566E150-240 UNITS

*Unit is factory-supplied with holding charge only.

†Typical operating charge with 25 ft of interconnecting piping. Operating charge is approximate for

maximum system capacity.

**Storage capacity is measured at liquid saturated temperatures of 120 F.

UNIT

566E150

566E180

566E240

NOMINAL CAPACITY (tons)

12

1

/

2

15

20

OPERATING WEIGHTS (lb)

Aluminum-Fin Coil (Standard)

676

740

764

Copper-Fin Coil (Optional)

822

886

904

REFRIGERANT TYPE*

R-22

Operating Charge, Typical (lb)†

23

23

28

Shipping Charge (lb)

3.1

3.1

3.1

COMPRESSOR

Scroll

Qty...Model

2...ZR72

2...ZR94

2...ZR125

Speed (rpm)

3500

3500

3500

Oil Charge (oz)

60 (ea)

85 (ea)

110 (ea)

Crankcase Heater Watts

70

CONDENSER FANS

Qty...Rpm

2...1075

Diameter (in.)

26

Nominal Hp

1

/

2

Nominal Airflow (cfm, total)

11,000

Watts (total)

1460

CONDENSER COIL

Rows...Fins/in.

3...15

Face Area (sq ft)

29.2

Storage Capacity (lb)**

48

CONTROLS

Pressurestat (psig)

High Pressure

Cutout

426 ± 7

Cut-in

320 ± 20

Low Pressure

Cutout

27 ± 4

Cut-in

67 ± 7

FAN CYCLING CONTROLS

Operating Pressure (psig)

No. 2 Fan, Close

255 ± 10

Open

160 ± 10

PRESSURE RELIEF

Location

Liquid Line

Temperature (F)

200

PIPING CONNECTIONS (in. ODM)

Suction

(2) 1

3

/

8

Liquid

(2)

1

/

2

Hot Gas Stub

3

/

8

5

0TF

Q0

04-

0

1

2

56
6D

/E
150

-2
40

Advertising
This manual is related to the following products: