ELECTRICAL DATA (cont)

524A-B,C ALTERNATE MOTORS

LEGEND

*Motors are designed for satisfactory operation within 10% of nominal

voltages shown. Voltages should not exceed the limits shown in the
Voltage Limits column.

NOTES:

1. Minimum circuit amps (MCA) and MOCP values are calculated in

accordance with NEC (National Electrical Code) Article 440.

2. Motor FLA values are established in accordance with UL (Under-

writers’ Laboratories) Standard 1995.

3. Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply voltage
is greater than 2%. Use the following formula to determine the per-
centage of voltage imbalance.
% Voltage Imbalance

Example: Supply voltage is 460-3-60.

AB = 393 v
BC = 403 v
AC = 396 v

= 397

Determine maximum deviation from average voltage.

(AB) 397 – 393 = 4 v
(BC) 403 – 397 = 6 v
(AC) 397 – 396 = 1 v

Maximum deviation is 6 v.

Determine percent of voltage imbalance.

% Voltage Imbalance = 100 x

= 1.5%
This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than
2%, contact your local electric utility company immediately.

UNIT

524A-B
524A-C

V*-PH-Hz

VOLTAGE

LIMITS

FAN MOTOR

POWER SUPPLY

Hp (kW)

FLA

Minimum Circuit

Amps

MOCP

072

208/230-1-60

187-253

2.4 (1.79)

11.0

13.8

20

208/230-3-60

187-253

2.9 (2.16)

7.5

9.4

15

460-3-60

414-506

2.9 (2.16)

3.4

4.3

15

575-3-60

518-632

2.0 (1.49)

2.3

2.9

15

090

208/230-1-60

187-253

2.4 (1.79)

11.0

13.8

15

208/230-3-60

187-253

2.9 (2.16)

7.5

9.4

15

460-3-60

414-506

2.9 (2.16)

3.4

4.3

15

575-3-60

518-632

3.0 (2.24)

3.8

4.8

15

120

208/230-3-60

187-253

3.7 (2.76)

10.2

12.8

20

460-3-60

414-506

3.7 (2.76)

4.8

6.0

15

575-3-60

518-632

3.0 (2.24)

3.8

4.8

15

150

208/230-3-60

187-253

3.7 (2.76)

10.2

12.7

20

460-3-60

414-506

3.7 (2.76)

4.8

6.0

15

575-3-60

518-632

5.0 (3.73)

5.1

6.4

15

180

208/230-3-60

187-253

5.0 (3.73)

14.6/12.8

18.3/16.0

30/25

460-3-60

414-506

5.0 (3.73)

6.4

8.0

15

575-3-60

518-632

5.0 (3.73)

5.1

6.4

15

240

208/230-3-60

187-253

7.5 (5.59)

21.5/19.4

26.9/24.3

45/40

460-3-60

414-506

7.5 (5.59)

9.7

12.1

20

575-3-60

518-632

7.5 (5.59)

7.8

9.8

15

300

208/230-3-60

187-253

10.0 (7.46)

28.2/26.8

35.3/33.5

60/60

460-3-60

414-506

10.0 (7.46)

13.4

16.8

30

575-3-60

518-632

10.0 (7.46)

10.3

12.9

20

FLA

Full Load Amps

MOCP — Maximum Overcurrent Protection

= 100 x

max voltage deviation from average voltage

average voltage

Average Voltage =

393 + 403 + 396

3

=

1192

3

6

397

50
TF
Q00

4

-012

52
4A0

7

2-
30
0