Error messages, A p p e n d i x a, Appendix a error messages – ETC CEM3 v1.5.1 User Manual

Page 53

Advertising
background image

A

Error Messages

47

Appendix A
Error Messages

The table below lists all of the possible error/status messages that may be listed on the

CEM3 display followed by the probably cause and any possible corrective action to remedy

the error.

If you have any problems resolving errors, or do not feel comfortable performing them,

contact ETC Technical Services (see

Help from ETC Technical Services, page 3

).

W A R N I N G :

To avoid the possibility of electric shock, power must be turned OFF before

removing dimmer or control modules. Prior to any action that involves

removing any module, de-energize main feed to dimmer rack and follow

appropriate Lockout/Tagout procedures as described in NFPA Standard

70E. It is important to note that electrical equipment such as dimmer racks

can present an arc flash safety hazard if improperly serviced. This is due to

available large short circuit currents on the feeders of the equipment. Any

work on energized equipment must comply with OSHA Electrical Safe

Working Practices.
Phase voltages inside the rack can be deadly, therefore only qualified

technicians should be allowed to remove modules and expose the inside of

the dimmer rack.

Message

Cause

Possible Corrective Action

Ambient Temp High

The temperature detected at the CEM3 has
exceeded the limit set under the “Temp High
Warn” option in [Setup]->Rack

Decrease ambient temperature, or adjust
temperature warning level. Ensure that fan is
functioning properly.

CPU Temp Low

The temperature detected at the CEM3 is
below 0C (32F)

Increase room temperature

DMX Error Port A

The DMX signal on port A is corrupt or invalid Check DMX wiring and termination

DMX Error Port B

The DMX signal on port B is corrupt or invalid Check DMX wiring and termination

No DMX Port A

No DMX signal is detected on port A

Check DMX wiring, termination or transceiver
chip

No DMX Port B

No DMX signal is detected on port B

Check DMX wiring, termination or transceiver
chip

Frequency Error

The power frequency is out the supported
range of 47-63Hz

Check the incoming power supply to the rack.
Contact a qualified electrician.

Phase A, B, or C
Error

The power on the indicated phase could not be
interpreted due to noise or interference

Check the incoming power supply to the rack.
Contact a qualified electrician.

Phase A, B, or C Off No power is detected on the indicated phase.

Check the incoming power supply to the rack.
Contact a qualified electrician.

Temp Sensor Stuck

The temperature sensor is giving an invalid
reading

Replace or service CEM3

Zero Cross Error

The dimming engine is unable to detect the
power zero cross correctly

Check the incoming power supply/Service or
replace CEM3. Power cycle the rack.

Phase A, B, or C
Volts High

The power on the indicated phase is above the
volts high warning level (in [Setup]->Rack)

Check the incoming power supply to the rack.
Contact a qualified electrician.

Phase A, B, or C
Volts Low

The voltage on the indicated phase is below
the minimum required value for the CEM3

Check the incoming power supply to the rack.
Contact a qualified electrician.

Phase A, B, or C
Overvolts

The voltage on the indicated phase is above
the maximum value for the CEM3

Check the incoming power supply to the rack.
Contact a qualified electrician.

Rack Memory Error

The CEM3 is unable to communicate with the
memory chip on the backplane

Check the CEM3 is seated correctly; Replace
backplane