I/O compound modules − digital I/O
Two relay outputs − EPM−S308

3

l

108

EDSIO1000 EN 7.0

Technical data

EPM−S308: rated data

Module identifier

265

dec

Current consumption/power loss

Current consumption from backplane bus

130 mA

Power loss

0.7 W

Relay outputs

Number of outputs

2

Load voltage

Nominal value

DC 30 V / AC 230 V

Total current

for each group, horizontal structure,
40°C

3 A

for each group, horizontal structure,
60°C

3 A

for each group, vertical structure

3 A

Output current

for "1" signal, nominal value

3 A

Maximum switching capacity

Service life

Parallel switching of outputs

for redundant control

Not possible

for power increase

Not possible

Control of a digital input

Not possible

Switching frequencies

for ohmic loads

Max. 100 Hz

Output data size

8 bits (with EPM−S110: 2 bits)