DeviceNet communication

Parameterising the counter

One counter 32 bits, 24 V DC − EPM−S600

11

l

585

EDSIO1000 EN 7.0

Additional functions Description

Main counting
direction

The main counting direction can be parameterised:
None: The whole counting range is available.
Forwards: Limitation of the counting range upwards. The counter counts from the
parameterised loading value in the positive direction to the parameterised final value −1
and then skips to the loading value again with the encoder pulse that is following.
Backwards: Limitation of the counting range downwards. The counter counts from the
parameterised loading value in the negative direction to the parameterised final value +1
and then skips to the loading value again with the encoder pulse that is following.

Gate function

The gate function serves to start, stop, and interrupt a counting function. In the case of
this counter a differentiation between the internal gate (I−gate), hardware gate (HW
gate), and software gate (SW gate) is made.

l

The I−gate is the AND logic operation of the software gate (SW gate) and the hardware
gate (HW gate).

l

The SW gate is controlled via your user program (status word in the output area).

l

The HW gate is controlled via the digital gate input.

The following response can be parameterised:
Cancelling gate function:After closing the gate and opening it again, the counting process
continues from the loading value again.
Interrupting gate function:After closing the gate and opening it again, the counting
process continues with the last current counter content.

Latch function

If a positive edge occurs at the latch input, the current count value is stored in the latch
register. The latch register is accessed via the input area. After a STOP−RUN transition,
latch is always 0.

Comparator

You can specify a comparison value which, depending on the count value, activates the
digital output or triggers a process alarm.

Hysteresis

By specification of a hysteresis you can for instance prevent the output from being
permanently switched if the value of an encoder signal fluctuates around the comparison
value.

Process alarm

The activation of a process alarm can be parameterised. A process alarm can be triggered
in the case of the following events:

l

Hardware gate open

l

Hardware gate closed

l

Counting limit − overflow

l

Counting limit − underflow

l

Comparison value reached

l

Final value reached

l

Latch value reached

Diagnostic alarm

If the diagnostic alarm is enabled in the parameter setting, it occurs if another process
alarm is triggered for the same event during a process alarm processing

.

,

Further information can be found in the chapter "Product description".