15 loading the default setting, Canopen communication – Lenze I/O system 1000 System Manual User Manual

Page 341

Advertising
background image

CANopen communication

Loading the default setting

8

l

341

EDSIO1000 EN 7.0

8.15

Loading the default setting

All parameter changes are reset to the default setting via index I1011

hex

.

The default setting is accepted by switching the supply off and on again. Changes that you
may have carried out before will be deleted from the EEPROM of the I/O system.

Index

Name

Possible settings

Important

Lenze Selection

I1011

h

¿

Restore All
Parameters

0

Resetting the parameter setting
in the EEPPROM of the bus
coupler to the Lenze setting.
Function in accordance with
CANopen (DS301/DS401
communication protocol).

^ 340

0

Number of subindexes assigned

Read only
Number of the subindexes used
by the index 1011

h

1 Load

0 = no function
1684107116

d

= load Lenze setting

The numerical value is
ASCII−coded and complies with:
64 61 6F 6C

h

= "D" "A" "O" "L"

After executing "Load",
acceptance is effected by

l

Voltage off/on, or

l

Transmission of a reset node
telegram (00 82 xx, mit xx =
node address)