PROFIBUS communication

Setting the parameters of analog I/O
2 analog inputs −10 ... +10 V (16 bits) − EPM−S406

9

l

402

EDSIO1000 EN 7.0

9.5.5

2 analog inputs −10 ... +10 V (16 bits) − EPM−S406

Parameter data

During the execution time you can access the parameter data via the following data sets:

Data set

Name

Description/value

Lenze

No.

Byte

0

1

Reserved

0

2

Limit value
monitoring

Bit 0: Channel 1 (0 = deactivated; 1 = activated)
Bit 1: Channel 2 (0 = deactivated; 1 = activated)
Bits 7 ... 2: Reserved

00

h

1

0

Interference
frequency suppression

Bit 1, 0: Channel 1

00: Deactivated
01: 60 Hz
10: 50 Hz

Bit 3, 2: Channel 2

00: Deactivated
01: 60 Hz
10: 50 Hz

Bits 7 ... 4: Reserved

00

h

128

0

Function channel 1

12 (12

h

): −10 ... 10 V / −27648 ... 27648

dec

34 (22

h

): −10 ... 10 V / −16384 ... 16384

dec

16 (10

h

): 0 ... 10 V / 0 ... 27648

dec

32 (20

h

): 0 ... 10 V / 0 ... 16384

dec

255 (FF

h

): channel deactivated

20

h

1

Reserved

0

2

Upper limit value
channel 1

Value from the rated range; if this value is exceeded and
the limit value monitoring function is active, a process
alarm is triggered.
7FFF

h

: Limit value alarm deactivated

7FFF

h

3

Lower limit value
channel 1

Value from the rated range; if the actual value falls below
this value and the limit value monitoring function is
active, a process alarm is triggered.
8000

h

: Limit value alarm deactivated

8000

h

129

0

Function channel 2

12 (12

h

): −10 ... 10 V / −27648 ... 27648

dec

34 (22

h

): −10 ... 10 V / −16384 ... 16384

dec

16 (10

h

): 0 ... 10 V / 0 ... 27648

dec

32 (20

h

): 0 ... 10 V / 0 ... 16384

dec

255 (FF

h

): channel deactivated

20

h

1

Reserved

0

2

Upper limit value
channel 2

Value from the rated range; if this value is exceeded and
the limit value monitoring function is active, a process
alarm is triggered.
7FFF

h

: Limit value alarm deactivated

7FFF

h

3

Lower limit value
channel 2

Value from the rated range; if the actual value falls below
this value and the limit value monitoring function is
active, a process alarm is triggered.
8000

h

: Limit value alarm deactivated

8000

h

With the formulas listed in the following you can convert a digital value into an analog
output value and vice versa.